Operation
P74x/EN OP/Na7
MiCOM P741, P742, P743
(OP) 5-
15
OP
The 87BB trip order can be blocked in the PU using 2 logic inputs, one to block the phase
element, the second to block the SEF element:
•
INP Block 87BB/P
•
INP Block 87BB/N
If some PUs are connected to Voltage device and not the other ones, some PU can trip
whereas the other ones are blocked by the voltage criteria coming from the Voltage device.
1.2.8.4 Busbar Protection Tripping Time delays
1.2.8.4.1 Busbar Protection Tripping Time delay in the CU
In the CU, the 87BB tripping time can be delayed by a settable time, the fault has to be
detected by the phase element only.
That allows, for example the clearance of the fault by a fuse on the fault feeder before
tripping the whole zone.
1.2.8.4.2 Busbar Protection Tripping Time delay in a PU
In all the PUs, the 87BB tripping time can be delayed by a settable time.
That allows, for example in Generation, a sequential tripping of all feeders connected to the
faulty zone.
1.2.8.5 Busbar Protection Tripping order PU logic
In all the PUs, there are options to block the 87BB protection trip order coming from the CU.
The logic is based either on the I>2 high set phase overcurrent function or on the IN>2 high
set neutral overcurrent function, each with the following options:
•
Phase and earth fault element (87BBP&N blocking),
•
Only the 87BB phase element (87BB/P blocking),
•
Only the 87BB SEF element (87BB/N blocking),
•
A combination of the different functions (I>2 & 87BBP&N, I>2 & 87BB/P, I>2 & 87BB/N).
The 87BB blocking function have a settable drop-off timer from 200ms to 6s by step of
100ms.
1.3
Additional protections
1.3.1
Dead Zone protection (DZ)
On a feeder, if the isolators or the breaker is open, a dead zone (or end zone) is said to exist
between the open element and the CT. The P74x peripheral units can protect this zone with
the Dead Zone protection. This is a simple time delayed overcurrent and earth fault element
which is only active when a dead zone is identified in the local topology.
1.3.2
Stub protection
When a one and half breaker scheme is protected by a P74x, the stub protection can be
done using a simple time delayed overcurrent element in each PU.
The activation of this protection has to be set in the PSL and activated when all the
associated isolators are open.
In the main setting group (usually 1), there is no overcurrent protection, in the next setting
group (usually 2) this overcurrent is enabled (on top of the same setting as in the main
setting group).
The setting group will be changed from “main” to “next” in the PSL.
Summary of Contents for P741
Page 2: ......
Page 4: ......
Page 6: ...P74x EN IT Na7 Introduction MiCOM P741 P742 P743 ...
Page 8: ...P74x EN IT Na7 Introduction IT 1 2 MiCOM P741 P742 P743 IT ...
Page 18: ...P74x EN TD Na7 Technical Data MiCOM P741 P742 P743 ...
Page 30: ...P74x EN TD Na7 Technical Data TD 2 14 MiCOM P741 P742 P743 TD ...
Page 32: ...P74x EN GS Na7 Getting Started MiCOM P741 P742 P743 ...
Page 70: ...P74x EN ST Na7 Getting Started MiCOM P741 P742 P743 ...
Page 72: ...P74x EN ST Na7 Settings ST 4 2 MiCOM P741 P742 P743 ST ...
Page 116: ...P74x EN OP Na7 Operation MiCOM P741 P742 P743 ...
Page 120: ...P74x EN OP Na7 Operation OP 5 4 MiCOM P741 P742 P743 OP ...
Page 136: ...P74x EN OP Na7 Operation OP 5 20 MiCOM P741 P742 P743 OP FIGURE 8 CB FAIL LOGIC ...
Page 166: ...P74x EN AP Na7 Application Notes MiCOM P741 P742 P743 ...
Page 234: ...P74x EN PL Na7 Programmable Logic MiCOM P741 P742 P743 ...
Page 290: ...P74x EN PL Na7 Programmable Logic PL 7 56 MiCOM P741 P742 P743 PL ...
Page 291: ...Programmable Logic P74x EN PL Na7 MiCOM P741 P742 P743 PL 7 57 PL ...
Page 292: ...P74x EN PL Na7 Programmable Logic PL 7 58 MiCOM P741 P742 P743 PL ...
Page 294: ...P74x EN PL Na7 Programmable Logic PL 7 60 MiCOM P741 P742 P743 PL ...
Page 295: ...Programmable Logic P74x EN PL Na7 MiCOM P741 P742 P743 PL 7 61 PL ...
Page 296: ...P74x EN PL Na7 Programmable Logic PL 7 62 MiCOM P741 P742 P743 PL ...
Page 298: ...P74x EN PL Na7 Programmable Logic PL 7 64 MiCOM P741 P742 P743 PL ...
Page 299: ...Programmable Logic P74x EN PL Na7 MiCOM P741 P742 P743 PL 7 65 PL ...
Page 300: ...P74x EN PL Na7 Programmable Logic PL 7 66 MiCOM P741 P742 P743 PL ...
Page 302: ...P74x EN MR Na7 Measurements and Recording MiCOM P741 P742 P743 ...
Page 324: ...P74x EN FD Na7 Firmware Design MiCOM P741 P742 P743 ...
Page 344: ...P74x EN FD Na7 Firmware Design FD 9 20 MiCOM P741 P742 P743 FD FIGURE 10 P74x SYSTEM OVERVIEW ...
Page 351: ...Firmware Design P74x EN FD Na7 MiCOM P741 P742 P743 FD 9 27 FD ...
Page 353: ...P74x EN CM Na7 Commissioning MiCOM P741 P742 P743 ...
Page 429: ...P74x EN MT Na7 Maintenance MiCOM P741 P742 P743 ...
Page 431: ...P74x EN MT Ma7 Maintenance MT 11 2 MiCOM P741 P742 P743 MT ...
Page 451: ...P74x EN TS Na7 Troubleshooting MiCOM P741 P742 P743 ...
Page 453: ...P74x EN TS Na7 Troubleshooting TS 12 2 MiCOM P741 P742 P743 TS ...
Page 475: ...P74x EN SC Na7 SCADA Communications MiCOM P741 P742 P743 ...
Page 499: ...P74x EN SC Na7 SCADA Communications SC 13 24 MiCOM P741 P742 P743 SC ...
Page 501: ...P74x EN SG Na7 Symbols and Glossary MiCOM P741 P742 P743 ...
Page 511: ...P74x EN SG Na7 Symbols and Glossary SG 14 10 MiCOM P741 P742 P743 SG Logic Gates ...
Page 513: ...P74x EN IN Na7 Installation MiCOM P741 P742 P743 ...
Page 515: ...P74x EN IN Na7 Installation IN 15 2 MiCOM P741 P742 P743 IN ...
Page 528: ...Installation P74x EN IN Na7 MiCOM P741 P742 P743 IN 15 15 IN FIGURE 6 P742 40TE REAR VIEW ...
Page 533: ...P74x EN VH Na7 Firmware and Service Manual Version History MiCOM P741 P742 P743 ...
Page 542: ...APPENDIX A WIRING DIAGRAMS ...
Page 543: ...Appendix A Wiring Diagrams P74x P74x EN M Na7 ...
Page 559: ......