P74x/EN OP/Na7
Operation
(OP) 5-
6
MiCOM P741, P742, P743
OP
The other advantage of using an instantaneous sum lies in the speed of decision, which in
turn is dictated by the sampling frequency.
Differential currents may also be generated under external fault conditions due to CT error.
To provide stability for through fault conditions the relay adopts a biasing technique, which
effectively raises the setting of the relay in proportion to the through fault current thereby
preventing relay maloperation.
The bias current is the scalar sum of the currents in the protected zone and for the check
zone. Each of these calculations is done on a per phase basis for each node and then
summated.
1.1.2.1 Bias Characteristic and Differential current
The operation of the busbar differential protection is based on the application of an algorithm
having a biased characteristic, (Figure 2) in which a comparison is made between the
differential current and a bias or restraining current. A trip is only permitted if this differential
current exceeds the set slope of the bias characteristic. This characteristic is intended to
guarantee the stability of protection during external faults where the scheme has current
transformers with differing characteristics, likely to provide differing performance.
The algorithm operands are as follows:
Differential Current
i
diff
(t) =
Σ
i
Bias or Restraining current
i
bias
(t) =
Σ
i
Slope of the bias characteristic
kx
Tripping permitted by bias element for:
i
diff
x(t) >
kx x i
bias
(t)
The main differential current element of P74x will only be able to operate if the differential
current reaches a threshold
I
D
x>2. In general, this setting will be adjusted above the normal
full load current.
1.1.2.2 Scheme supervision by "check zone” element
The use of a "check zone" element is based on the principle that in the event of a fault on
one of the substation busbars, the differential current measured in the faulty zone will be
equal to that measured in the entire scheme.
One of the most frequent causes of maloperation of differential busbar protection schemes is
an error in the actual position of an isolator or CB in the substation to that replicated in the
scheme (auxiliary contacts discrepancy). This would produce a differential current in one or
more current nodes. However, if an element monitors only the currents "entering" and
"leaving" the substation, the resultant will remain negligible in the absence of a fault, and the
error will lie with the zone’s assumption of the plant position at this particular point in time.
Summary of Contents for P741
Page 2: ......
Page 4: ......
Page 6: ...P74x EN IT Na7 Introduction MiCOM P741 P742 P743 ...
Page 8: ...P74x EN IT Na7 Introduction IT 1 2 MiCOM P741 P742 P743 IT ...
Page 18: ...P74x EN TD Na7 Technical Data MiCOM P741 P742 P743 ...
Page 30: ...P74x EN TD Na7 Technical Data TD 2 14 MiCOM P741 P742 P743 TD ...
Page 32: ...P74x EN GS Na7 Getting Started MiCOM P741 P742 P743 ...
Page 70: ...P74x EN ST Na7 Getting Started MiCOM P741 P742 P743 ...
Page 72: ...P74x EN ST Na7 Settings ST 4 2 MiCOM P741 P742 P743 ST ...
Page 116: ...P74x EN OP Na7 Operation MiCOM P741 P742 P743 ...
Page 120: ...P74x EN OP Na7 Operation OP 5 4 MiCOM P741 P742 P743 OP ...
Page 136: ...P74x EN OP Na7 Operation OP 5 20 MiCOM P741 P742 P743 OP FIGURE 8 CB FAIL LOGIC ...
Page 166: ...P74x EN AP Na7 Application Notes MiCOM P741 P742 P743 ...
Page 234: ...P74x EN PL Na7 Programmable Logic MiCOM P741 P742 P743 ...
Page 290: ...P74x EN PL Na7 Programmable Logic PL 7 56 MiCOM P741 P742 P743 PL ...
Page 291: ...Programmable Logic P74x EN PL Na7 MiCOM P741 P742 P743 PL 7 57 PL ...
Page 292: ...P74x EN PL Na7 Programmable Logic PL 7 58 MiCOM P741 P742 P743 PL ...
Page 294: ...P74x EN PL Na7 Programmable Logic PL 7 60 MiCOM P741 P742 P743 PL ...
Page 295: ...Programmable Logic P74x EN PL Na7 MiCOM P741 P742 P743 PL 7 61 PL ...
Page 296: ...P74x EN PL Na7 Programmable Logic PL 7 62 MiCOM P741 P742 P743 PL ...
Page 298: ...P74x EN PL Na7 Programmable Logic PL 7 64 MiCOM P741 P742 P743 PL ...
Page 299: ...Programmable Logic P74x EN PL Na7 MiCOM P741 P742 P743 PL 7 65 PL ...
Page 300: ...P74x EN PL Na7 Programmable Logic PL 7 66 MiCOM P741 P742 P743 PL ...
Page 302: ...P74x EN MR Na7 Measurements and Recording MiCOM P741 P742 P743 ...
Page 324: ...P74x EN FD Na7 Firmware Design MiCOM P741 P742 P743 ...
Page 344: ...P74x EN FD Na7 Firmware Design FD 9 20 MiCOM P741 P742 P743 FD FIGURE 10 P74x SYSTEM OVERVIEW ...
Page 351: ...Firmware Design P74x EN FD Na7 MiCOM P741 P742 P743 FD 9 27 FD ...
Page 353: ...P74x EN CM Na7 Commissioning MiCOM P741 P742 P743 ...
Page 429: ...P74x EN MT Na7 Maintenance MiCOM P741 P742 P743 ...
Page 431: ...P74x EN MT Ma7 Maintenance MT 11 2 MiCOM P741 P742 P743 MT ...
Page 451: ...P74x EN TS Na7 Troubleshooting MiCOM P741 P742 P743 ...
Page 453: ...P74x EN TS Na7 Troubleshooting TS 12 2 MiCOM P741 P742 P743 TS ...
Page 475: ...P74x EN SC Na7 SCADA Communications MiCOM P741 P742 P743 ...
Page 499: ...P74x EN SC Na7 SCADA Communications SC 13 24 MiCOM P741 P742 P743 SC ...
Page 501: ...P74x EN SG Na7 Symbols and Glossary MiCOM P741 P742 P743 ...
Page 511: ...P74x EN SG Na7 Symbols and Glossary SG 14 10 MiCOM P741 P742 P743 SG Logic Gates ...
Page 513: ...P74x EN IN Na7 Installation MiCOM P741 P742 P743 ...
Page 515: ...P74x EN IN Na7 Installation IN 15 2 MiCOM P741 P742 P743 IN ...
Page 528: ...Installation P74x EN IN Na7 MiCOM P741 P742 P743 IN 15 15 IN FIGURE 6 P742 40TE REAR VIEW ...
Page 533: ...P74x EN VH Na7 Firmware and Service Manual Version History MiCOM P741 P742 P743 ...
Page 542: ...APPENDIX A WIRING DIAGRAMS ...
Page 543: ...Appendix A Wiring Diagrams P74x P74x EN M Na7 ...
Page 559: ......