Appendix 1: Reporting codes in Contact ID or SIA
Table 37
Event codes
lists the event codes sent for different reports (if enabled) when using Contact
ID or SIA formats. The numbers in brackets following the event is the number that is reported as the
zone number. If there are no parentheses, the zone is
0
. An asterisk represents the first character from
the event code of the zone that is bypassed or in fault.
Table 37. Event codes
Report
Contact
ID
SIA
Report
Contact ID
SIA
Manual test
601
RX
Keypad tamper
137
TA
Autotest
602
RP
Keypad panic (audible)
120
PA
Open (user number)
401
OP
Keypad panic (silent)
120
PA
Close (user number)
401
CL
Duress
121
HA
Cancel (user number)
406
OC
Keypad auxiliary 1
110
FA
Start program
627
LB
Keypad auxiliary 2
100
MA
End program
628
LX
RF sensor lost (zone number)
381
*T
Recent close (user number)
401
CR
RF sensor restore (zone
number)
381 *R
Exit error (user number)
457
EE
Sensor low battery (zone
number)
384 XT
Event log full
605
JL
Sensor battery restore (zone
number)
384 XR
Fail to communicate
354
RT
Zone fault (zone number)
380
*T
Expander fault (device
number)
333 ET Zone fault restore (zone
number)
380 *R
Expander restore (device
number)
333
ER
Zone tamper (zone number)
137
TA
Telephone fault
351
LT
Zone tamper restore (zone
number)
137 TR
Telephone restore
351
LR
Zone bypass (zone number)
570
*B
Siren tamper (device
number)
321
YA
Bypass restore (zone number)
570
*U
Siren restore (device
number)
321
YH
Near Alarm (A/B Alarm)
138
BM
Aux power over current
(device number)
312 YP Early
open/late
close 451
OK