NX-10 Installers manual
233
Connecting the NX-586E to a panel
Connect the cable with alligator clips to a NX-10 panel as follows:
•
Red to POS
•
Black to COM
•
Green to DATA
Programming the NX-586E direct connect module
Figure 29. NX-586E menu structure
The control panel’s programming memory can be copied to one of the four programming memories
in the NX-586E direct connect module and vice-versa. You must enrol and default the module before
you begin to program the system. For more information on enrolling and defaulting, see Chapter B7
Enrolling modules
.
To program the NX-586E using the NX-1048 keypad, select
Installer Menu>NX-586E Direct
Connect Module.
To program the NX-586E using a PC, start the DL900 up/download software on
the PC.
Note:
It is recommended to up/download data when the keypad is in the operating mode only (not in the
programming mode). If you are in the Installer Menu the keypad can time out and start copying process
which will interfere with or stop up/downloading in progress.
Enabling memory transfer using the keypad
The following example uses the NX-1048 keypad to copy the control panel’s programming memory
to the NX-586E programming memory 2. It then copies programming information from the NX-
586E programming memory 3 to the control panel.
1.
Navigate with the
½¾
keys to
NX-586E Direct Connect Module>Files
and press
OK
.
2.
To write information from the control panel to the NX-586E, scroll to
File 2>Panel to
File
and press
OK
.
3.
Select
Yes
to confirm and press
OK
.
4.
The control panel’s programming memory is copied to the NX-586E direct connect
module’s programming memory 2. The Receiving Data LED on the NX-586E direct
connect module flashes while the data is received. The keypad sounder chimes when the
operation is successful.
5.
To read information from the NX-586E to the control panel, scroll to
File 3>File to
Panel
and press
OK
.
6.
Select
Yes
to confirm and press
OK
.
7.
The information in the NX-586E programming memory 3 is copied to the current control
panel. The Sending Data LED on the NX-586E direct connect module flashes while the
data is received. The keypad sounder chimes when the operation is successful.
Files
File 1
Panel Type
Panel to File
File to Panel
Options
Speed
13.1
13.2
13.1.
13.2.1
13.1.1.
13.1.1.2
13.1.1.3
Files 2 - 4
Same as above