16
—
Controller and Remote Controller Function Manual and Operating Instructions
7.1 Controller and Remote Controller Function Manual 1
7.1.1 Temperature Parameters
◆
Indoor preset temperature (T
preset
)
◆
Indoor ambient temperature (T
amb.
)
◆
Outdoor condenser temperature (T
cond.
)
7.1.2 Basic Functions
Under any mode, the compressor will keep running within 6 minutes once it is started (except under overfull protection).
Once stopped, it cannot be restarted until after 3-minute delay. When outdoor fan is started, run at high speed for 8
seconds and then switch to desired speed.
7.1.2.1 Cooling Mode
7.1.2.1.1 Cooling Conditions and Process
When T
amb.
≥
T
preset
+1
℃
, the unit will run under cooling mode, in which case the compressor and outdoor fan will be
started and the indoor fan will run at low speed.
When T
amb
≤
T
preset
-1
℃
, the unit will be stopped under cooling mode, in which case the compressor and outdoor fan will
be stopped and the indoor fan will run at preset speed.
When T
preset
-1
℃
<T
amb.
< T
preset
+1
℃
, the unit will maintain its original operating status.
¾
Under this mode, the switchover valve will be de-energized and the temperature can be set within a range from 16 to
30
℃
.
7.1.2.2 Dehumidifying Mode
7.1.2.2.1 Working Conditions and Process of Dehumidifying
When T
amb.
> T
preset
+2
℃
, the unit will run under cooling mode, in which case the compressor and outdoor fan will be
started and the indoor fan will run at low speed.
When T
preset
-2
℃≤
T
amb.
≤
T
preset
+2
℃
, the compressor, indoor unit and outdoor fan will run 6 minutes and stop 4 minutes
in repeated cycle, while the indoor fan will run at low speed.
When T
amb.
< T
preset
-2
℃
, the compressor, outdoor fan and indoor fan will be stopped.
¾
Under dehumidifying mode, the temperature can be set within a range from 16 to 30
℃
.
7
T
amb
T
preset
+1
℃
T
preset
-1
℃
Start cooling
Original operating status
Stop cooling
6 min.
Preset speed
Run
Stop
6 min.
3 min.
T
amb
T
preset
+2
℃
T
preset
-2
℃
Cooling
Stop cooling
Run
Stop
Low speed
Dehumidifying
Compressor
Indoor fan
Outdoor fan
Compressor
Indoor fan
Outdoor fan
6 min.
6 min.
4 min.
4 min.
Summary of Contents for AIR C18
Page 2: ......
Page 3: ......
Page 5: ... 2 Model Remarks GE AIR C24 Communication Ceiling Mounted Unit 1PH 230V 50Hz R407C ...
Page 14: ... 11 Applicable to GE AIR C24 OUT Unit mm Over 600 Bolt Nut Wrench ...
Page 15: ... 12 Applicable to GE AIR C34 C41 OUT 378 Unit mm Over 600 Bolt Nut Wrench ...
Page 17: ... 14 Electrical Diagram GE AIR C18 GE AIR C24 6 ...