CS875-575-375-275-175 Installers Manual with CS5500 keypad
B.2.11
2.7.1 Setting timers
You can set timers to control the duration of various system functions. The following example sets the internal
siren timer to five minutes. When the siren starts ringing, the timer starts counting down. When the timer is
finished, the siren automatically cuts out.
1.
Ensure the advanced menu is enabled. See chapter 20 for more information.
2.
Navigate with the
µ¶
keys to
Control Panel>System Settings
and press
OK
.
3.
Scroll to
Timers>Sounders>Internal Siren Timeout
and press
OK
.
4.
Enter
5
and press
OK
.
5.
The keypad beeps once to confirm the change and returns to
Internal Siren Timeout
.
2.7.2 Configuring system features
You can specify various system features, enable the tests that can be performed on the control panel and set clock
options. The following example programs the control panel to activate the siren and make a manual test call to the
central station during the do self tests.
1.
Ensure the advanced menu is enabled. See chapter 20 for more information.
2.
Navigate with the
µ¶
keys to
Control Panel>System Settings
>
Feature Select
and press
OK
.
3.
Scroll to
Diagnostics>Manual Siren Test>Enabled
and press
OK
.
4.
The keypad beeps once to confirm the change and returns to
Manual Siren Test
.
5.
Scroll to
Manual Dialler Test
>
Enabled
and press
OK
.
6.
The keypad beeps once to confirm the change and returns to
Manual Dialler Test
.
2.8 Setting arm schedules
The control panel can be programmed to automatically open and close partitions at specified times on specified
days. To program schedules, you must enable the advanced menu. Select
Installer Menu>Commands>Advanced
Menu>Enabled
and press
OK
. Then select
Installer Menu>Control Panel>Arm Schedules.
2.8.1 Setting up schedules
You can set up a schedule to control the opening and autoarming events for each partition. The following example
sets a schedule for partition 1 so that it is automatically closed at 18.00 on a Monday if there is no activity in the
building. If there is activity at closing time, the control panel will try to arm after every 45 minutes of inactivity
until the next opening time, or until the system is armed manually.
Partitions Opening
(1) Partition 1
Schedule Times
Partitions Autoarming
Closing/Autoarm
Opening
(1) Partition 1
2.7.1
2.7.2
2.7.3
2.7.1.1
2.7.2.1
2.7.3.1
2.7.3.2
2.7.1.1.1
2.7.1.1.2
2.7.1.1.3
2.7.1.1.4
2.7.1.1.5
2.7.1.1.6
2.7.1.1.7
2.7.2.1.1
2.7.2.1.2
2.7.2.1.3
2.7.2.1.4
2.7.2.1.5
2.7.2.1.6
2.7.2.1.7
2.7.2.1.8
2.7.3.1.1
2.7.3.1.2
2.7.3.2.1
2.7.3.2.2
Hour
Minute
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Hour
Minute
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
45 Minute Retry
Partitions 2 - 8
Same as above
Partitions 2 - 8
Same as above