CS875-575-375-275-175 Installers Manual with CS5500 keypad
B.6.1
Chapter 6: Setting up the CS208H / CS208 / CS216
6.1 Overview
The CS208H, CS208 and CS216 input expanders can provide extra wired zones for a CSx75 control panel. Each
CS208H and CS208 input expander can provide up to 8 extra wired zones. Each CS216 input expander can
provide up to 16 wired zones. Each CS208 / CS216 input expander has an optional tamper switch and power
isolator. Each CS208H input expander has a tamper switch and power isolator.
6.2 CS208 / CS216 input expander
The CS208 input expander and CS216 input expander are similar. The only difference is the number of zones
provided. The illustration below shows the CS216 input expander.
6.2.1 Installing the
CS208 / CS216 input expander
6.2.2 Setting the DIP switches
1.
Power down the CS208 / CS216 input expander.
2.
Decide the starting zone of each input expander. The starting zone of each zone expander must be on a
boundary of 8 zones.
3.
To set the starting zone, set the DIP switches from Table 6-1:
CS208 / CS216 input expander DIP switches
.
The zones for this module begin from this starting zone number.
1
Zone connections (16 sets)
5
No function
2
Tamper connection (required)
6
Supervision LED
3
Keypad bus connection
7
DIP switches (6 positions)
4
Additional keypad bus connection
8
Processor