CS875-575-375-275-175 Installers Manual with CS5500 keypad
A.3.2
shielded cable should be used and the cable should be connected to a GND terminal at the control panel end
only
.
3.
The remote bus cable is used for communication between the control panel and the keypads/expanders. The
greatest care should be taken when installing this cable.
Never
split it into separate cables. Do not use cables
with wires that are used for telephone connections or for switching, for example, flashing lights, sirens or
relays.
4.
For mains power connection, use the mains connector terminal either through a permanent wiring or a
flexible mains cable to an earthed mains outlet. Always use cable ties to fix the mains cable, at the dedicated
fixing point provided near the mains terminal connector.
•
In case of permanent fixed wiring, insert an easily accessible, dedicated bipolar circuit breaker in the power
distribution network.
•
Never attempt to solder a mains connection wire’s end where they will be wired to the terminal connectors.
5.
Avoid loops of wire inside the control panel and route cables so they do not lie on top or underneath the
printed circuit board. The use of cable ties is recommended and improves neatness within the box.
6.
The battery used with this unit, must be made of materials of suitable flammability class (HB or better).
7.
Any circuit connected either directly to the on-board relay’s contact or to the external relay’s contact
through the on-board electronic output, must be of
SELV
(
Safety extra-low voltage
) operating circuit.
•
The mains switching relay must not be fitted inside the control panel cabinet.
•
Always place a suppression diode (for example, a 1N4001) across the relay coil.
•
Use only a relay with good insulation between the contacts and the coil.
8.
The minimum clearance between equipment closures is 50 mm between equipment vents.
9.
Only use units in a clean environment and not in humid air.
3.5 Defaulting the panel
IMPORTANT:
Before installing and programming the system, default the panel to ensure that you have the
correct country defaults according to your local regulations.
3.6 Using the DIP switch diagrams
•
When the DIP switch is set to the ON position, the switch is
at the top. This is illustrated in the DIP switch diagrams as
ON
•
When the DIP switch is set to OFF, the switch is at the
bottom. This is illustrated in the DIP switch diagram as
OFF
•
In this example the first, third and sixth DIP switches are ON
and the second, fourth and fifth DIP switches are OFF.
•
The DIP switch diagram demonstrates this as shown.