50
Figure 38: Outputs Page
The Outputs page is divided into three sections, one for each of the three types of hardware
outputs available – relays, solenoids, and Analog Outputs.
4.4.14.1 Relays
Each of the four available relays has three parameters associated with it. The relay parameters
are described in Table 14.
Table 14: Relay Configuration
Parameter
Explanation
ID
The hardware ID for the relay on the IO board. The ID number for the relay in the
web GUI is the same as the relay number printed on the IO board.
Description
Provides a description of the relay’s function (e.g. Normal / Fault). The
description can be edited by left clicking on the description, typing in the new
description, and pressing Enter.
Reverse Logic
If this option is chosen, the relay will be energized (NO and C) when inactive, and
de-energized (NC and C) when active. If the option is not selected, the relay will
be de-energized when inactive, and energized when active.
4.4.14.2 Solenoids
Each of the 8 available solenoids has three parameters associated with it. These parameters are
described in Table 15.
Table 15: Solenoid Configuration
Parameter
Explanation
ID
The hardware ID for the solenoid on the IO board. The ID number for the
solenoid in the web GUI is the same as the solenoid number printed on the IO
board.