BMS INTEGRATION
Hydronic-PURE-Control-UserManual-211214
SECTION 7
7-6
Modbus
Scope
Description
Size
Notes
Units
40067
R
Boiler 1 LL Position
INT16
0 – Waiting
1 – Disabled
2 – Not Available
3 – Lead
4 – Lag 1
5 – Lag 2
6 – Lag 3
7 – Lag 4
8 – Lag 5
9 – Lag 6
10 – Lag 7
11 – Lag 8
12 – Lag 9
14 – Lag 1 (T)
15 – Lag 2 (T)
16 – Lag 3 (T)
17 – Lag 4 (T)
18 – Lag 5 (T)
19 – Lag 6 (T)
20 – Lag 7 (T)
21 – Lag 8 (T)
22 – Lag 9 (T)
N/A
40068
R
Boiler 2 LL Position
INT16
N/A
40069
R
Boiler 3 LL Position
INT16
N/A
40070
R
Boiler 4 LL Position
INT16
N/A
40071
R
Boiler 5 LL Position
INT16
N/A
40072
R
Boiler 6 LL Position
INT16
N/A
40073
R
Boiler 7 LL Position
INT16
N/A
40074
R
Boiler 8 LL Position
INT16
N/A
40075
R
Boiler 9 LL Position
INT16
N/A
40076
R
Boiler 10 LL Position
INT16
N/A
40077
R
Boiler 1 LL Status
INT16
0 – O
ffline
1 – Alarm
2 – Switch O
ff
3 – Standby
4 – Call for Heat
5 - Modulating
N/A
40078
R
Boiler 2 LL Status
INT16
N/A
40079
R
Boiler 3 LL Status
INT16
N/A
40080
R
Boiler 4 LL Status
INT16
N/A
40081
R
Boiler 5 LL Status
INT16
N/A
40082
R
Boiler 6 LL Status
INT16
N/A
40083
R
Boiler 7 LL Status
INT16
N/A
40084
R
Boiler 8 LL Status
INT16
N/A
40085
R
Boiler 9 LL Status
INT16
N/A
40086
R
Boiler 10 LL Status
INT16
N/A
40087
R
Boiler 1 LL Firing Rate
INT16
0.0 – 100.0 [Note 1]
%
40088
R
Boiler 2 LL Firing Rate
INT16
0.0 – 100.0 [Note 1]
%
40089
R
Boiler 3 LL Firing Rate
INT16
0.0 – 100.0 [Note 1]
%
40090
R
Boiler 4 LL Firing Rate
INT16
0.0 – 100.0 [Note 1]
%
40091
R
Boiler 5 LL Firing Rate
INT16
0.0 – 100.0 [Note 1]
%
40092
R
Boiler 6 LL Firing Rate
INT16
0.0 – 100.0 [Note 1]
%
40093
R
Boiler 7 LL Firing Rate
INT16
0.0 – 100.0 [Note 1]
%
40094
R
Boiler 8 LL Firing Rate
INT16
0.0 – 100.0 [Note 1]
%
40095
R
Boiler 9 LL Firing Rate
INT16
0.0 – 100.0 [Note 1]
%
40096
R
Boiler 10 LL Firing Rate
INT16
0.0 – 100.0 [Note 1]
%
40097
R
Current Setpoint Mode
INT16
0 – Outdoor Reset Curve
1 – BMS Analog 4-20mA
2 – BMS Analog 0-10VDC
3 – BMS Network
4 – Manual
N/A
40098
W
BMS Network Setpoint
INT16
40.0 – 185.0 [Note 1]
F
40099
R
Maximum Setpoint
INT16
40.0 – 185.0 [Note 1]
F
40100
R
Minimum Setpoint
INT16
40.0 – 185.0 [Note 1]
F
40101
R
Outdoor Air Cutoff
INT16
40.0 – 185.0 [Note 1]
F
40102
R
Outdoor Air Cutoff Reset
INT16
40.0 – 185.0 [Note 1]
F
40103
W
BMS Enable
INT16
0 – Not Enabled
1 – Enabled
[Note 5]
N/A