SECTION 3
Hydronic-PURE-Control-UserManual-211214
CONTROL MENUS
!
WARNING
All information in this addendum is
for reference and guidance purposes,
and does not substitute for required
professional training, conduct, and strict
adherence to applicable jurisdictional/
professional codes or regulations.
Follow all proper lockout/tagout
procedures for service. Before beginning
any service, ensure area is free of
combustible materials and other dangers.
In order to meet warranty conditions,
ensure all appropriate maintenance
activities are performed.
Delta T Protection (EDR+ Boilers Only)
This modifier is mandatory and cannot be turned off or configured at the Fulton
Control. As the delta T limit is approached, a factory-designated PID is used to
slow the firing rate in an attempt to not pass the delta T limit. It’s designed to
keep the boiler within the factory-specified operating requirements. Please see
the
Installation and Operation
manual for these operating requirements.
`
MODE 1
When above 30% firing rate, the delta T limit is factory set to 40
°
F (100
°
F
capable).
`
MODE 2
When below 30% firing rate, the delta T limit is linearly changed based on
firing rate from 30% to low fire to stay within compliance of minimum flow rate
requirements.