CONTROL MENUS
Hydronic-PURE-Control-UserManual-211214
SECTION 3
3-4
Parameter Name
Range
Unit
Description
Wiring
Modbus
Register
Boiler Status
0 - Safety Lock Out
2 - Safety Phase
10 - LMV Home Run
12 - Standby
22 - Fan Motor
24 - Air Damper
30 - Prepurging
36 - Air Damper
38 - Preignition
39 - Testing Pressure Switch
40 - Fuel Valve
42 - Ignition
44 - Interval 1
50 - Safety Time 2
52 - Interval 2
60-62 - Running
70-72 - Afterburn Time
74-78 - Postpurge Time
80 - Evacuation of Test Space
81 - Atmospheric Pressure Test
82 - Filling of Test Space
83 - Gas Pressure Test
90 - Gas Shortage Waiting Time
91 - Limit String Open
N/A
Status and Phase number from
the LMV3.
3-Wire Shielded Modbus
Factory Wired D+/D-/SG
40000
INT16
Read
Control
0 - L/L Waiting
1 - Disabled
2 - Not Available
3 - L/L: Lead
4 - L/L: Lag 1
5 - L/L: Lag 2
6 - L/L: Lag 3
7 - L/L: Lag 4
8 - L/L: Lag 5
9 - L/L: Lag 6
10 - L/L: Lag 7
11 - L/L: Lag 8
12 - L/L: Lag 9
13 - L/L: Lag 10
14 - L/L: Lag 1 (T)
15 - L/L: Lag 2 (T)
16 - L/L: Lag 3 (T)
17 - L/L: Lag 4 (T)
18 - L/L: Lag 5 (T)
19 - L/L: Lag 6 (T)
20 - L/L: Lag 7 (T)
21 - L/L: Lag 8 (T)
22 - L/L: Lag 9 (T)
23 - L/L: Lag 10 (T)
24 - Local
25 – Manual
N/A
Lead/Lag Status
(T) Designates a temporary
position where the boiler will
take a normal place in the Lead/
Lag sequence after the next call
for heat.
*Boilers must be connected and
configured for the Lead/Lag
feature in order to be assigned a
Lead/Lag position.
*If communication is lost be-
tween boilers in a Lead/Lag setup
they will revert back to individu-
al/local control.
CAT5e Ethernet Cable from pass-
through port on back of the electri-
cal panel
Field Wired between boilers for a 2
boiler setup -or- if 3 or more boil-
ers then use the factory supplied
Ethernet Switch
Factory Wired from Fulton Control-
ler Port 1
40001
INT16
Read
Modulation
0 - Normal Rate
1 - Low Fire Hold
2 - Cold Start
3 - Freeze Protection
4 - Delta T Protection
5 - Outlet Soft Limit
6 - Venting Limitation
N/A
Designates which modifier if any
are active.
*See PID Control Section for
modifier descriptions
N/A
(Determined by Fulton Controller)
40002
INT16
Read
Modulation
Target
0.0 – 100.0
%
Desired Modulation rate as cal-
culated by the Fulton controller
being sent to the LMV3.
3-Wire Shielded Modbus from
LMV3
Factory Wired D+/D-/SG
40003
INT16
Read
Rate
0.0 – 100.0 %
%
Actual Firing Rate as read back
from the LMV3.
3-Wire Shielded Modbus
Factory Wired D+/D-/SG
40004
INT16
Read
Flame Signal
0.0 – 100.0 %
%
Flame signal as seen by the UV
scanner and read back from the
LMV3.
3-Wire Shielded Modbus Fac-
tory Wired D+/D-/SG
40005
INT16