CONTROL MENUS
Hydronic-PURE-Control-UserManual-211214
SECTION 3
!
WARNING
This addendum is specific to the usage
of the
Hydronic PURE Control™
and
should be used in conjunction with
the current version of the respective
boiler’s Installation and Operation
manual. Both should be read in their
entirety and be made permanently
available to the staff responsible for
equipment operation.
This addendum should not be
considered as a complete guide, nor
should it replace existing guides or
standards which may be applicable.
Fulton reserves the right to change
any part of this addendum and
the corresponding Installation and
Operation manual without notice.
Do not install, operate, service
or repair any component of this
equipment unless you are qualified
and fully understand all requirements
and procedures.
All information in this addendum is
for reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes or
regulations.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch.
• Do not use any phone in your building.
• Immediately call your gas
supplier from a neighbor’s phone.
• Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier,
call the fire department.
A qualified installer, service agency
or the gas supplier, must perform
installation and service.
Auxiliary Configuration
Used for advanced setup and user selectable options, as shown in the two menus
and table that follows.
.
Parameter
Name
Range
Units
Description
System Piping
Isolation Valve
System Pumps
Boiler Pump
N/A
Select optional system components that will be
controlled by the boiler.
Note that only one pump control option can be
selected at a time.
Venting Material
AL 29-4C / 316L
Polypropylene
N/A
Select to match the venting material installed for
the boiler. This will automatically adjust the High
Stack Limit Temperature lockout temperature.
Screen Saver
N/A
N/A
Allows the user to turn on/off the screen saver.
Boiler Name
N/A
N/A
User labeling for the boiler.
Site Elevation
0 - 9999
feet
(above
sea level)
Used by the controller as part of the O2 monitor-
ing. Setting this up incorrectly can cause nui-
sance warnings for O2 sensor operation.
Lead/Lag
N/A
N/A
Select to enable Lead/Lag for this boiler.
See The Lead / Lag section and addendum 2 for
setup and more information.
Alarm Horn
N/A
N/A
Turns the screens built in alarm horn on/off.
2nd Low Water
N/A
N/A
Let’s the controller know if a 2nd low water probe
has been wired and enables annunciation and
alarms for it.
Domestic Water
N/A
N/A
Enables the DHW capabilities of controller. When
selected a new button will appear on the screen
for DHW configuration.