Domestic Hot Water Configuration
Accessible only when
Domestic Water
is selected on the
Auxiliary
Configuration
page. Allows control of a DHW pump based on an RTD
temperature input.
The DHW call for heat occurs them Domestic Start temperature is reached,
and ends when Domestic Stop temperature is reached. The DHW pump runs
continuously during the DHW call for heat, ending after the prescribed time
delay off. If the current setpoint is below the Domestic Minimum, the setpoint
will be bumped to the Domestic Minimum.