Modbus
Scope
Description
Size
Notes
Units
40104
W
BMS Heartbeat
INT16
An integer 1 must be written to this point con-
tinuously
N/A
Table Notes:
1. The decimal poin
t is fixed to the tenths place, but not transmitted. For example, a value of 1000 equals 100.0
2. The value is only writable when the program has been set to accept a BMS communication signal, see program
documentation for individual details
3. Refer to alarm chart for index number definition. Alarm index is only active when the active alarm value is equal to 1
4. This connection refers to the local boiler network required for Lead/Lag connectivity. Not all boilers will be available. For
instance if you only have 5 boilers in your system, boilers 6 through 10 will show as not connected and should be ignored.
5. Physical jumper in panel must be removed in order to use this network enable point.
Alarm List
Information on “Alarm Info Screen”
Alarm Index
Alarm Name
Alarm Screen
Description
Alarm Screen Solution
Error Code
Error Diagnostic
Code
Alarm Originator
Alarm Notes
0
No flame at the
end of TSA
No flame at the end
of TSA1
2
1
LMV
1
No flame at the
end of TSA
No flame at the end
of TSA2
2
2
LMV
2
No flame at the
end of TSA
No flame at the end
of TSA1 (SW version
<=V02.00)
2
4
LMV
3
Air pressure
failure
Air pressure swit
ch off
3
0
LMV
4
Air pressure
failure
Air pressure switch on
3
1
LMV
5
Air pressure
failure
Evaluation air pres-
sure switch
Correct setting of
parameter 235 or 335.
(Deactivation of air
pressure switch during
operation only permit-
ted for pneumatic
operation!).
3
2
LMV
6
Air pressure
failure
Air pressure on? pre-
vention of startup
3
4
LMV
7
Air pressure
failure
Air pressure, combus-
tion pressure - pre-
vention of startup
3
20
LMV
8
Air pressure
failure
Air pressure, POC -
prevention of startup
3
68
LMV
9
Air pressure
failure
Air pressure, combus-
tion pressure, POC -
prevention of startup
3
84
LMV
10
Extraneous light
Extraneous light dur-
ing startup
4
0
LMV