Questions? Please Contact Your Local Manufacturer’s Representative
3-39
SECTION 3
Hydronic-PURE-Control-UserManual-211214
CONTROL MENUS
!
WARNING
All information in this addendum is
for reference and guidance purposes,
and does not substitute for required
professional training, conduct, and strict
adherence to applicable jurisdictional/
professional codes or regulations.
Follow all proper lockout/tagout
procedures for service. Before beginning
any service, ensure area is free of
combustible materials and other dangers.
In order to meet warranty conditions,
ensure all appropriate maintenance
activities are performed.
Current
Setpoint
-50.0 – 250.0
F
N/A
Current Setpoint
as determined
by the Fulton
Controller.
Field wiring
may be
required
depending on
what source is
selected.
40024
INT16
Read
Minimum
Setpoint
40.0 – 185.0
F
80.0
Absolute
minimum setpoint
that the unit will
control to regard-
less of source or
scaling.
*Reference only.
Must be changed
from the Setpoint
Configuration
Screen.
N/A
N/A
BMS Analog
Setup and Scaling for BMS hardwire signals.
Parameter
Name
Range
Units
Factory
Default
Description
Wiring
Modbus
Register
Current
Signal
(4-20mA)
0.0 – 20.0
mA
N/A
Displays the
4-20mA signal as
received by the
Fulton controller.
Field wired
to customer
connections
TB4-A1/TB4-A2.
N/A
Current
Signal
(0-10VDC)
0.0 – 10.0
VDC
N/A
Displays the
0-10VDC signal as
received by the
Fulton controller.
Field wired
to customer
connections
TB4-A3/TB4-A4.
N/A
Setpoint
20mA
40.0 – 185.0
F
180.0
High Scaling for
the 4-20mA signal.
Field wired
to customer
connections
TB4-A1/TB4-A2.
N/A
Setpoint
4mA
40.0 – 185.0
F
100.0
Low Scaling for
the 4-20mA signal.
Field wired
to customer
connections
TB4-A1/TB4-A2.
N/A