CONTROL MENUS
Hydronic-PURE-Control-UserManual-211214
SECTION 3
!
WARNING
This addendum is specific to the usage
of the
Hydronic PURE Control™
and
should be used in conjunction with
the current version of the respective
boiler’s Installation and Operation
manual. Both should be read in their
entirety and be made permanently
available to the staff responsible for
equipment operation.
This addendum should not be
considered as a complete guide, nor
should it replace existing guides or
standards which may be applicable.
Fulton reserves the right to change
any part of this addendum and
the corresponding Installation and
Operation manual without notice.
Do not install, operate, service
or repair any component of this
equipment unless you are qualified
and fully understand all requirements
and procedures.
All information in this addendum is
for reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes or
regulations.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch.
• Do not use any phone in your building.
• Immediately call your gas
supplier from a neighbor’s phone.
• Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier,
call the fire department.
A qualified installer, service agency
or the gas supplier, must perform
installation and service.
Parame-
ter Name
Range
Units
Factory
Default
Description
Wiring
Modbus
Register
Pump
Control
Signal
Delta T
Delta P
N/A
Delta T
Selection for Sys-
tem Pump control
PID to be based
on Pressure or
Temperature.
Secondary Pump
1 Field Wiring
to TB4-C7, and
TB4-C8
Secondary Pump
2 Field Wiring to
TB4-C9, and TB4-
C10
0-10VDC Output
based on PID and
Delta T or Delta P
N/A
Lead
Hour
Rotate
0 – 1000
Hour(s)
0
How often the Lead
System pump will
rotate.
N/A
N/A
Setpoint
0.0 – 100.0
F Pres-
sure
0.0
Temperature or
Pressure setpoint
for the system
pump PID.
N/A
N/A
Alarm
Low
-50.0 – 100.0
F Pres-
sure
0.0
Pump alarm point
if Temperature or
Pressure goes be-
low the designated
point. The Fulton
Controller will
alarm and shut off
the running pump
and bring on the
Lag pump.
N/A
N/A
Alarm
High
0.0 – 100.0
F
Pres-
sure
Pump alarm point
if Temperature
or Pressure goes
above the desig-
nated point. The
Fulton Controller
will alarm and shut
off the running
pump and bring on
the Lag pump.
N/A
N/A