TX2550 M4
Upgrade and Maintenance Manual
81
Basic hardware procedures
4.6
Connecting the power cord
V
CAUTION!
The server supports a mains voltage in the range of 100 V to 240 V. You
may only operate the server if its rated voltage range corresponds to the
local mains voltage.
I
For 800 W Titanium PSU:
Mains input voltage range: 200 V – 240 V
Ê
Connect the power cords to the PSUs.
Ê
If applicable, connect the mains plugs to power outlets of the rack socket
strip.
I
To provide true phase redundancy, the second PSU should be
connected to a different AC power source from the other PSU. If one
AC power source should fail, the server will still continue to run.
Ê
Ensure that the status indicator on the PSU is lit green (see section
"Indicators on PSUs (slide-in units)" on page 512
Figure 34: Example: Locking the cable clamp of a PSU
Ê
Pull the cable clamp up (1).
Ê
Thread the power cord through the cable clamp (2).
Ê
Press the cable clamp down until it engages to secure the cable (3).
I
It will take about 60 seconds until the server can be powered on.
Summary of Contents for PRIMERGY TX2550 M4
Page 6: ...Upgrade and Maintenance Manual TX2550 M4 ...
Page 36: ...36 Upgrade and Maintenance Manual TX2550 M4 Before you start ...
Page 104: ...104 Upgrade and Maintenance Manual TX2550 M4 Basic hardware procedures ...
Page 136: ...136 Upgrade and Maintenance Manual TX2550 M4 Basic software procedures ...
Page 284: ...284 Upgrade and Maintenance Manual TX2550 M4 Hard disk drive HDD solid state drive SSD ...
Page 372: ...372 Upgrade and Maintenance Manual TX2550 M4 Processor CPU ...
Page 458: ...458 Upgrade and Maintenance Manual TX2550 M4 System board and components ...
Page 480: ...480 Upgrade and Maintenance Manual TX2550 M4 Converting a floorstand model to a rack model ...
Page 516: ...516 Upgrade and Maintenance Manual TX2550 M4 Appendix A ...
Page 518: ...518 Upgrade and Maintenance Manual TX2550 M4 Appendix B ...
Page 558: ...List of all used screws for PRIMERGY Servers Assembled in Germany and Japan January 2017 ...