Make a Manual Setting of a Monitoring Channel
Make a Manual Setting of a Monitoring Channel
Instruction
Follow these steps to activate and make a manual setting of a channel (Temp stator
ph 1 is an example):
1.
• Click Setup above the main (left) menu to enter setup mode.
• Click channel to setup (Temp stator ph 1).
Result:
The Temp stator ph 1 window is opened.
Note!
Rightclick and select Refresh to update the current page. Press F5 or click
the Refresh button to restart the entire web tool.
2.
Select sensor in the Sensor drop-down menu (Pt100 analog).
3.
• Enter alarm trip temperature for warning level High (130 °C) and for pump stop level
Very high (140 °C) in the Alarm settings
fi
eld.
• Select
Action priority
for each alarm level in the drop-down menus.
4.
• Select
Reset option
. A-alarms should be manually reset but B-alarms can be
allowed to reset automatically.
• Enter alarm
Delay
. Use a short delay for Broken circuit and Short circuit to reveal
glitches.
5.
Set Y-axis max value in the Graph settings
fi
eld to adjust the presentation of
measurement results with graphs.
6.
If the distance between the pump and the electrical cabinet is long (approximately
>30 meters), enter a
fi
gure to compensate for the measurement error due to
additional lead resistance in the Compensation for long leads
fi
eld.