First Setup Using the Operator Panel
First Setup Using the Operator Panel
Instruction
When setting up using the operator panel, use the operator panel
• menu system (see chapter
Use the Operator Panel
)
and
• menu navigation help.
Follow these steps to set up using the operator panel.
Step
Action
Detailed
instruction
in chapter
Settings with
the Operator
Panel
1
In the View menu, press down arrow and OK to enter the
Setup menu branch.
2
If you want to change the default language (English), press
OK to enter edit mode and select the desired language.
Change Display
Language
3
Enter the default password 1234 and login to the protected
part of the setup menus.
Result:
Menu Change password (2.4) is displayed.
Log in and
Change
Password
4
Go to General con
fi
g (2.5) and set the unit information:
• Date and time.
• Temperature unit (by default °C).
• MAS id (unit number)
Set Unit
Information
5
If there is
• a pump memory in the system, continue with step 6
•
no
pump memory in the system (for example for retro
fi
t
of a CAS), continue with step 7.
6
• Set communication to
Active
for the pump memory.
• Perform
Copy all from PM to MAS
.
Retrieve Sensor
Information from
Pump Memory
7
• If a Power analyzer (optional) is used, set its
communication to
Active
(EXT2).
• Use default parameters for baudrate, id and type.
See the Power
analyzer manual
on how to set the
analyzer
8
• If a Higher level controller (optional) is used, set its
communication to
Active
(EXT1).
• Select Modbus id to
fi
t into the Modbus network (MAS
units are Modbus slaves).
• Use the default baudrate.
9
• Check with your network administrator if you have to
set ethernet IP address or other ethernet parameters
for use on a LAN.
• Press Esc to leave General con
fi
g.
10
If you wish to add an extra monitoring channel or adjust
the settings, for example alarm trip limits or alarm delays,
for existing channels, use the menus 2.6–2.21 in the Setup
menu.
Make a Manual
Setting of a
Monitoring
Channel
55