Menu
number
Menu name/Description
2.6.2
Alarm limits
2.6.2.2
Very high (R > 750 ohm)/Very high (R > 3000 ohm)
2.6.2.6
Short circuit (R < 20 ohm)
2.6.3
Alarm action priority
2.6.3.2
Very high (Warning/Pump stop/Off)
2.6.3.6
Short circuit (Warning/Pump stop/Off)
2.6.4
Alarm reset option
2.6.4.2
Very high (Manual/Automatic)
2.6.4.6
Short circuit (Manual/Automatic)
2.6.5
Alarm delay
2.6.5.2
Very high (0 - 30s)
2.6.5.6
Short circuit (0 – 30s)
2.7
Temp stator ph 1
2.7.1
Sensor
2.7.1.1
Pt100//None
2.7.2
Alarm limits
2.7.2.1
Broken circuit (R > 250 ohm)
2.7.2.2
Very high (T > x°)
2.7.2.2.1
Setting of alarm limit
2.7.2.3
High (T > y°)
2.7.2.3.1
Setting of alarm limit
2.7.2.6
Short circuit (R < 60 ohm)
2.7.3
Alarm action priority
2.7.3.1
Broken circuit (Warning/Pump stop/Off)
2.7.3.2
Very high (Warning/Pump stop/Off)
2.7.3.3
High (Warning/Pump stop/Off)
2.7.3.6
Short circuit (Warning/Pump stop/Off)
2.7.4
Alarm reset option
2.7.4.1
Broken circuit (Manual/Automatic)
2.7.4.2
Very high (Manual/Automatic)
2.7.4.3
High (Manual/Automatic)
2.7.4.6
Short circuit (Manual/Automatic)
2.7.5
Alarm delay
2.7.5.1
Broken circuit (0 - 30s)
2.7.5.2
Very high (0 - 30s)
2.7.5.3
High (0 - 30s)
2.7.5.6
Short circuit (0 – 30s)
2.7.6
Compensation for long wires (value in ohm)
68