No.
Event
Cause
Action
9
Clock error
Clock circuit failure, lost backup
voltage
Set clock
10
File upload
error
Attempt to install program or
upload database failed
Attempt to upload again
11
New program
New program installed
No action
12
E-mail error
Error in E-mail settings
Check E-mail settings
13
E-mail test
Test email sent
No action
14
Pump mem.
com error
Pump memory communication
error
Check
• wiring
• communication LEDs
• setting Active/Inactive
under General con
fi
g –
RS485/Modbus
• for possible interference.
Reference
: See also
Problems Communicating with
another Unit
(Pump memory,
Operator panel, Relay module,
Power analyzer, PLC) in
section
Common Problems
and Solutions
.
15
Pump mem.
csum error
Pump memory error
If the message recurs,
contact your local ITT Flygt
organization.
16
No pump
memory sync
Pump serial number in Base
unit and Pump memory differ
Synchronize Pump memory
and MAS manually.
Reference
: See section
Copy
Data To/From Pump Memory
in chapter
Operation
.
17
Power an.
com error
Power analyzer communication
error
See Pump mem. com error
(no. 14) above
18
Reserved, not
in use
19
Reserved, not
in use
20
Op-panel com
error
Operator panel communication
error
See Pump mem. com error
(no. 14) above
21
Service
request
Service is requested according
to the user’s own setting
Reset MAS and perform
service of the pump
22
Database
erased
Database erased on command
No action
23
Relay mod.
com error
Relay Module, MRM 01,
communication error
See Pump mem. com error
(no. 14) above
147