![FLYGT MAS 711 Installation And Operation Manual Download Page 94](http://html1.mh-extra.com/html/flygt/mas-711/mas-711_installation-and-operation-manual_2311483094.webp)
Make Modem/PPP Settings
Purpose
The modem/PPP settings are used for direct connection between the computer and the
base unit using modem and PPP (point-to-point protocol). The settings must be done for
the unit to initiate a dial up connection, which is needed for the alarm distribution through
email to work when connected via a dial up modem connection.
Instruction
Follow these steps to make the modem/PPP settings:
1.
Click Setup — General con
fi
guration — Modem/PPP.
Result:
The Modem/PPP settings window is opened.
2.
• Enter the phone number to the ISP (internet service provider) providing the email
service.
• Enter time-out time, modem type and baudrate.
Comment:
A modem init text string capable of initiating most GSM or PSTN
modems is already entered by default (ATV1&D2&C1E1S0=1) in the Modem init
fi
eld. For certain types of modems, and for GPRS modems, this string might need to
be changed, see the modem documentation.
3.
• Set the gateway to be the same as the IP address above (to activate dial up).
Comment:
The PPP IP address is by default set to 192.168.48.95 and the netmask
to 255.255.255.0. These do usually not need to be changed.
94