2.0 USER INTERFACE
2-8
CyberCat 254/1016 Operation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-326-2
FM
2.2
PASSWORD PROTECTION
Access to the CyberCat system’s control and function buttons are restricted by the enclosure door. With the
door closed and locked, responding personnel can only view system events on the panel display and use the
accessible EVENT STEP buttons (if not covered by optional Lexan™) to filter through the systems event
history. Opening the enclosure door provides access to the systems Control and Function buttons, which
allows greater system operation capabilities. With the enclosure door open, responding personnel have the
ability to Silence or Acknowledge system events, initiate Drill commands and Reset the system. In addition,
the system operator has limited access to the systems menus and features without needing to enter a system
password.
Access to the CyberCat system’s menus is password protected to restrict access to those who require it.
Each CyberCat allows up to eight (8) User level passwords and a single System Administrator password to be
assigned by the system installer. The available security access levels are described as follows.
Password
Level
Designation
Privileges
Default
(door panel closed)
View system events on LCD display
Access to STEP buttons for reviewing system history
1
Customer
(door panel open – no
password entered)
All default privileges, plus:
Access to system control switches for executing system Drill,
Acknowledge, Silence and Reset
History menu (view only)
Diagnostic menus (view only)
Maintenance menu: Read Device and Device Address (all other menu
features are view only)
IR Communication (enable/disable)
2
USER
(Level 2 password entered –
eight available)
All default and Level 1 privileges, plus:
Configuration menus: Configuration check and set system time and
date (all other menu features are view only).
Maintenance menu: Device Replace, Walktest, Buzzer
Enable/Disable zones
Level 2 passwords are assigned during system configuration
3
SYSTEM ADMINISTRATOR
(Level 3 password entered)
All default, Level 1 and Level 2 privileges, plus:
Full access to all system menus
Default password is set by the factory prior to shipment. Can be
changed in the field.
Exhibit 2-9: Password Access Levels