5.0 SYSTEM DIAGNOSTICS
UL S2203
CyberCat 254/1016 Operation Manual
5-11
FM
P/N: 06-326-2
Rev 6, 09/2015
With the address selected, press the F2 button to display the Auxiliary Switch Cards diagnostics screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
F I R E - P H O N E I N T E R F 0 3
B
A U X I L I A R Y S W C A R D S
C
C A R D 1 : Y E S C A R D 2 : N O
D
C A R D 3 : N O C A R D 4 : N O
Exhibit 5-16: Auxiliary Switch Cards Diagnostics Screen
•
Row A – Displays “Fire-Phone Interf” and the address of the peripheral device.
•
Row C & D (CARD
n
) – Displays whether the auxiliary switch card is present (YES) or not present
(NO). Upper case “YES” or “NO” means the card is being supervised by the associated fire-
phone switch card. Lower case “yes” or “no” means the card is not being supervised.
5.5.5
VESDANET COMMUNICATIONS
The VESDAnet Communications screen allows you to view the communication status between the CyberCat
controller and the VESDA high level interface (HLI). From the Diagnostic Menu 2 screen, press the F5 button
to view the VESDAnet Communications screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
V E S D A Z O N E N U M : 0 0 1
B
P O L L T X : 0 0 0 0 R X : 0 0 0 0
C
N E T W T X : 0 0 0 0 R X : 0 0 0 0
D
C O M M I N T E R V A L : 1 0 0 0 M S
Exhibit 5-17: VESDAnet Communication Screen
•
Row A – Allows you to select the VESDA zone (device) number to display.
•
Row B (Poll TX) – Displays the number of polling transmissions sent to the VESDA zone selected
on Row A.
•
Row B (Poll RX) – Displays the number of polling receptions received from the VESDA zone
selected in Row A.
•
Row C (Netw TX) – Displays the number of network alarm requests sent from the panel to the
HLI.
•
Row C (Netw RX) – Displays the number of network alarms sent from the HLI to the panel.
•
Row D (COMM INTERVAL) - Allows you to adjust the communication rate between the CyberCat
and the VESDA HLI. Configurable from 250msec (fastest) to 2000msec (slowest). Default value
is 1000msec (1 second). A Level 4 (Factory) password is required to change this setting. Use
the +/- buttons to increment or decrement the field value.
Pressing the ENTER button while in this screen will clear the TX and RX counters for the selected VESDA
zone.