1.0 INTRODUCTION
1-40
CyberCat 254/1016 Operation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-326-2
FM
Exhibit 1-38: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Switch Card
20-Zone
Relay Action Settings (Selection table active for Smoke Control only)
Relay Action
Y
None
/ On / Auto / Off
1,2
Action Start
Y
Action starts with
confirmation address OR
delay timer
/ Action starts with
confirmation address AND
delay timer
Confirmation Address
Y
Panel:
0
- 128
Loop:
0
- 4
Address:
0
- 254
Relay Address
Y
Panel:
0
- 128
Loop:
0
- 4
Address:
0
- 254
Delay Timer
Y
0
– 255 seconds
Delay (timer) Start
Y
Delay timer starts
immediately
/ Delay timer
starts after confirmation
address activates
Zone Assignments (Selection table active for Voice Functions only)
Select Zones
Y
1 – 254
Selection Options
Y
Select / Clear
Y
All Zones / Even Zones / Odd
Zones
Y
Between:
1
– 254
Y
And: 1 –
254
Y
Any Zone (check box)
Y
Select All / Clear All / Invert
All
Notes:
1.
On and Off overrides up to 25 addressable relays on the panel’s SLCs.
2.
Auto returns up to 25 addressable relays back to automatic configured state.