5.0 SYSTEM DIAGNOSTICS
5-4
CyberCat 254/1016 Operation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-326-2
FM
5.4.1.2
DEVICE SERIAL NUMBER DIAGNOSTIC
The Device Serial Number Diagnostic screen allows you to compare the serial number stored in the panel for
the specific address to the serial number of the actual device present/found on the signaling line circuit (SLC).
From the Device Diagnostic Menu, press the F2 button to display the Device Serial Number Diagnostic
screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
L O O P : N A D D R E S S : 0 0 1
B
T Y P E : T Y P E O F D E V I C E
C
S E R I A L # S T O R E D P A N E L
D
S E R I A L # D E V I C E L O O P
Exhibit 5-4: Device S/N Diagnostic Screen
•
Row A (LOOP) -
allows you to select the loop number, represented by ‘N’. Use the ◄► buttons
to position the cursor under the field; then press the +/- buttons to change to desired loop (1-4).
•
Row A (ADDRESS) - A
llows you to select the address of the device to display. Use the ◄►
buttons to position the cursor under the field; then press the +/- buttons to increment/decrement
the address selection.
•
Row B - Displays the type of device connected to the panel for the loop and address in Row A.
•
Row C- Displays the serial number of the device held by the panel for supervision of the loop and
address displayed in Row A.
•
Row D - Displays the serial number of the device physically connected to the loop and address
displayed in Row A.
Note:
Row C and D should match or a multiple device trouble will be reported.