5.0 SYSTEM DIAGNOSTICS
UL S2203
CyberCat 254/1016 Operation Manual
5-27
FM
P/N: 06-326-2
Rev 6, 09/2015
5.8.4
FAAST DETECTOR STATUS
The FAAST Detector Status screen allows you to view the current status levels transmitted by the detector to
the panel. From the Diagnostic Menu 5 screen, press the F4 button to view the FAAST Detector Selection
screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
1 - 0 0 1 : F A A S T D E T E C T O R
B
P R E S S E N T E R T O V I E W
C
F A A S T S T A T U S
D
* * R E A D I N G * *
Exhibit 5-36: FAAST Detector Selection Screen
•
Row A – Allows you to select the loop (1 – 4) and address number (1 – 253) of the FAAST
detector that will be displayed.
Use the ◄► arrow buttons to position the cursor over the field; then
press the +/– buttons to change the value at cursor.
Rows B, C, and D will be blank until a valid
FAAST detector loop and address is selected in Row A; then Rows B and C will indicate “PRESS
ENTER TO VIEW FAAST STATUS”. Press the ENTER button to initiate the device read. Row D
will indicate “**READING**” to confirm initiation of the device read operation. Once the device
read is complete, the FAAST detector status screen will be displayed.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
L - A D D S F : * L V : T I M :
B
C F G : A S P : F D : L E D : 0
C
D I S : D I R : * F U : A I R F L O
D
C O M : D B L : F M : 0 0 0 %
Exhibit 5-37: FAAST Detector Status Screen
•
Row A (L-ADD) – Displays the loop (1 – 4) and address number (1 – 253) of the FAAST device
being displayed.
•
An asterisk (*) will be displayed in each status field when the applicable fault is active:
SF (Sensor Fault) – Sensor fault has occurred.
LV (Low Voltage) – Voltage supplied to detector has dropped to minimum operating range.
TIM (Time) – Detectors internal time has not been set.
CFG (Configuration Fault) – Detector has not been configured.
ASP (Aspirator Fault) – Detector aspirator has stopped functioning.
FD (Filter Door Open) – Filter door has been removed and not replaced.
LED (N/A LED is on or off) – Press F1 to toggle this LED on (1) or off (0).
DIS (Disable) – Detector has been disabled.
DIR (Drift Fault – IR Laser) – The IR sensor has reached its allowable drift limit.
FU (Filter Urgent) – Detector filter has been clogged for more than 72 hours.
COM (Communication) – Peripheral communication has failed and device is not functioning
properly.
DBL (Drift Fault – Blue LED) – The LED sensor has reached it allowable drift limit.
FM (Filter Minor) – Detector filter is clogged and needs to be changed.
AIRFLO (Airflow) – Detectors airflow has increased or decreased by 20% or greater. Airflow
percentage is indicated by ‘000%’.