1.0 INTRODUCTION
UL S2203
CyberCat 254/1016 Operation Manual
1-5
FM
P/N: 06-326-2
Rev 6, 09/2015
Exhibit 1-3: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
MISC.
Silence Options
Unsilence Time
Y
1-
24
hours
Silence Reminder
Y
Enabled /
Disabled
Silence Inhibit
Y
Enabled /
Disabled
Positive Alarm Sequence
Y
Enabled /
Disabled
Silence Mode
Y
UL
1
Time
Functions
Alarm Sensitivity Changes
Daytime Sensitivities start/stop
Y
12:00 AM – 12:00 AM
Days that use daytime sensitivity
Y
Sunday – Saturday
Use Daylight Savings Time
Y
Enabled
/ Disabled
Holiday Schedule
Night time sensitivity
Y
20 days total (mm/dd/yyyy)
4
DACT Auto Test
DACT Auto test start hour
Y
0 – 23
(2 default)
DACT Auto test period (hrs.)
Y
0
– 24 (0, 6, 12, 24 hrs.)
NAC
P10 and P11 (NAC 1 & NAC 2)
Sync Protocol
Y
NO
/ Gentex / System
Sensor /
2,3
State (Activation)
Y
Alarm
/ Pre-Alarm 1 / Pre-
Alarm 2 / Supervisory /
Trouble / Process
Silenceable
Y
Silenceable
/ Non
silenceable
Zone Assignment
Y
1 –
254
Circuit
Y
Enabled
/ Disabled
Drill
Y
Enabled
/
Disabled
Walktest
Y
Enabled
/
Disabled
Panel Sync Protocol
Y
Gentex /
System Sensor
/
Gentex – Visual Silence/
System Sensor – Visual
Silence
Relays
P2 Main Board Relays
Relay Selection
Y
R1
/ R2
5
State (Activation)
Y
Alarm
/ Pre-Alarm 1 / Pre-
Alarm 2 / Supervisory /
Trouble / Process / Zone
Disable
Silenceable
Y
Non-Silenceable
/
Silenceable
Zone Assignment
Y
1 –
254
Circuit
Y
Enabled
/ Disabled
Drill
Y
Enabled
/
Disabled
Notes:
1.
An audible signal that has been silenced at the protected premises shall automatically resound and remain energized until silenced and
retransmitted the signal to any supervising station to which the original signal was transmitted, as applicable, at least once every 24 hours until
the condition is corrected and the product is restored to the normal supervisory condition.
2.
If synchronization is selected, both NAC circuits will use the same sync protocol.
3.
Refer to Fike document 06-186 for compatible sync protocol.
4.
Only allows the installer to assign the night time sensitivity to a different obscuration level than during normal working hours. No other functions
are affected or disabled.
5.
Allows on board relays to be configured from the default setting of Alarm for R1 and Supervisory for R2 to the states listed in State (Activation).