1. Installation CPV−DI02 and CPV−CS02
1−16
Festo P.BE−CPV−DI02−EN en 0704NH
CPV−DI02 (PROFIBUS−DP)
Use a twisted, screened 2−core cable for connecting the field bus.
Cable specification as per EN 50170 (cable type A):
surge impedance:
135
Ū
165 (3
Ū
20 MHz)
capacitance per unit length:
< 30 nF/km
loop resistance:
< 110 /km
core diameter:
> 0.64 mm
core cross−sectional area:
> 0.34 mm
2
Bus length
Exact specifications on the bus length can be found in the
next section and in the manuals for your control system.
CPV−CS02 (ABBCS31)
Refer to the PLC manual for your controller for the type of
cable to be used. Also take into account here the distances
and the field bus baud rate.
Summary of Contents for PROFIBUD-DP
Page 2: ......
Page 15: ...Installation CPV DI02 and CPV CS02 1 1 Festo P BE CPV DI02 EN en 0704NH Chapter 1...
Page 58: ...1 Installation CPV DI02 and CPV CS02 1 44 Festo P BE CPV DI02 EN en 0704NH...
Page 59: ...Commissioning CPV DI02 PROFIBUS DP 2 1 Festo P BE CPV DI02 EN en 0704NH Chapter 2...
Page 79: ...Diagnosis CPV DI02 PROFIBUS DP 3 1 Festo P BE CPV DI02 EN en 0704NH Chapter 3...
Page 107: ...Commissioning CPV CS02 ABB CS31 4 1 Festo P BE CPV DI02 EN en 0704NH Chapter 4...
Page 116: ...4 Commissioning CPV CS02 ABB CS31 4 10 Festo P BE CPV DI02 EN en 0704NH...
Page 117: ...Diagnosis CPV CS02 ABB CS31 5 1 Festo P BE CPV DI02 EN en 0704NH Chapter 5...
Page 131: ...Technical appendix A 1 Festo P BE CPV DI02 EN en 0704NH Appendix A...
Page 146: ...A Technical appendix A 16 Festo P BE CPV DI02 EN en 0704NH...
Page 147: ...Index B 1 Festo P BE CPV DI02 EN en 0704NH Appendix B...
Page 148: ...B Index B 2 Festo P BE CPV DI02 EN en 0704NH Contents B Index B 1...
Page 154: ...B Index C 8 Festo P BE CPV DI02 EN en 0704NH...