62
EN
Cod. 3542B230 - Rev. 00 - 02/2022
OMNIA S HYBRID H 3.2
Menu
Level 1
Menu
Level 2
Menu
Level 3
Menu
Level 4
Description
Lower
limit
Upper
limit
Remedy
Unit of
measure-
ment
Default
value
For Serviceman
8 Holiday
Setting
8.1 T1S H.A. H
The target water output temperature for heating
the room in holiday mode
20
25
1
°C
25
8.2 T5S H.A. DHW
DHW water heater temperature set point in
holiday mode
20
25
1
°C
25
For Serviceman
10 Restore
Factory Settings
10, 1 Restore Factory
Settings
Restore Factory Settings
Y
N
/
/
N
For Serviceman
11 Test Run
11.1 Test Run Enable
TEST RUN ENABLE 0 = OFF 1 = ON - to enable
the menu “11.2 Trail run steps”
OFF
ON
/
/
OFF
11.2 Trail run steps
Point Check = to activate the menu “11.3 Point Check”
Air purge = ON - to activate the air bleed
Water pump = ON - to activate the water pump
Cooling = ON - to activate the cooling mode
Heating = ON -to activate the heating mode
Dhw = ON - to activate the DHW mode
Point Check / Air purge / Water pump / Cooling
/ Heating / Dhw
Point
Check
11.3 Point Check
3way-valve 1
TEST ON-OFF
Allows you to run a functional test on single loads, individually
forcing the activation and subsequent switching off.
Also allows you to temporarily force the system in specific
function modes for the test (air bleed, recirculation pump
running, etc.).
The switching on/off of each function is always done
manually.
It is only possible to enable/disable one function at a time; it is
not allowed at the same time.
If one function is active and you exit the Test Run menu while
it is active, the function will automatically switch off.
OFF
ON
/
/
OFF
3way-valve 2
OFF
ON
/
/
OFF
PUMPS
OFF
ON
/
/
OFF
PUMP
OFF
ON
/
/
OFF
PUMPC
OFF
ON
/
/
OFF
PUMPSOLAR
OFF
ON
/
/
OFF
PUMPDHW
OFF
ON
/
/
OFF
INNER BACKUP HEATER
OFF
ON
/
/
OFF
TANK HEATER
OFF
ON
/
/
OFF
3WAY-VALVE 3
OFF
ON
/
/
OFF
For Serviceman 14 Power Input
Limitation
14.1 POWER LIMITATION
To limit the power absorbed by the heat pump
(refer to “Table 11 - Max current input (A) for
different level of power input limitation" on page
63.
0
8
1
/
0
For Serviceman 15 Input Define
15.1 On/Off(M1M2)
Reserved
Yes
No
/
/
No
15.2 Smart Grid
Enables or disables SMART GRID
Yes
No
/
/
No
15.3 T1B(Tw2)
Enables or disables temperature probe T1B
(Tw2)
Yes
No
/
/
No
15.4 Tbt1
Enables or disables temperature probe Tbt1
Yes
No
/
/
No
15.5 Tbt2
Reserved
-
-
/
/
No
15.7 Solar Input
SOLAR ENABLE
Enables solar input
Yes
No
/
/
No
IN SOLAR
Type of solar input;
Tsolar (to enable the Tsolar solar panel probe
temperature);
SL1SL2 = do not use
Tsolar SL1SL2
/
/
SL1SL2
15.8 F-Pipe Length
Reserved
Yes
No
/
/
No
15.10 Rt/Ta_Pcb
Reserved
Yes
No
/
/
No
For Serviceman 17 FW Update
USB
17.1 Program fw
/
/
/
/
/
/
/
17.2 Verify Download --%
/
BMS address setting of the heat pump
1
16
1
/
0
NOTE
* It allows you to enable or disable the functions that can be restarted in the event of a power failure.