20
EN
Cod. 3542B230 - Rev. 00 - 02/2022
OMNIA S HYBRID H 3.2
Indoor unit technical data
06 / 10
UM
Power supply
220/240-1-50
V-ph-Hz
Exchanger type
Brazed stainless steel plate type
-
Type of pump
Electronic circulator (8 mca)
-
System expansion tank volume
10
l
System water safety valve calibration
3
bar
System hydraulic fittings
1” GAS F
-
DHW hydraulic fittings
3/4” GAS F
-
Refrigerant fittings / liquid line ***
3/8” SAE / Ø 9.52
-
Refrigerant fittings / gas line
5/8” SAE / Ø 15.88
-
Minimum system water content
15
l
Internal backup heater
3
kW
System temperature (min-max)
5 - 65
°C
System pressure (min-max)
1 - 3
bar
SWL - Sound power level indoor unit
39
39
39
39
dB(A)
Max absorbed current
1
A
Net weight
43
kg
Weight when working ****
45
kg
Weight of packaged unit
45
kg
***
For matching with external units mod. 4-6, an adapter from 3/8” SAE to 1/4” SAE is supplied for the liquid line Ø 6.35.
**** Weight refers to basic unit without accessories
3.2 ERP data
NOTE: Efficiency class calculated according to the European regulation 811/2013. The values refer to a unit without any optionals or accessories.
Model
4
6
8
10
UM
Efficiency class in
heating
low temperature (produced water 35°C)
186
191
200
201
ηs (%)
A+++
class
average temperature (produced water 55°C)
128
136
130
135
ηs (%)
A++
class
SEER
produced water 7°C
4.99
5.34
5.83
5.98
W/W
produced water 18°C
7.77
8.21
8.95
8.78
W/W
3.3 Heat pump operational limits
NOTE DHW MODE:
the produced water temperature is the tem-
perature of the water produced by the unit and not the DHW tem-
perature available to the user, which is a function of this parameter
and of the surface of the coil of the DHW cylinder, if any.
Operation range by heat pump with possible
limitation and protection.
-
-
-
-
-
-
Produced water temperature °C
Produced water temperature °C
External air temperature °C
External air temperature °C
DHW MODE
WARM MODE
Produced water temperature °C
External air temperature °C
COOL MODE
With IBH (system electric heater) installed.
With IBH (system electric heater) installed.
Operation range by heat pump with possible limita-
tion and protection.
Operation range by heat pump with possible limita-
tion and protection.
Maximum inlet water temperature line for heat
pump operation.
Maximum inlet water temperature line for heat
pump operation.