Before installing, check that the maximum length allowed has not been exceeded with a simple calculation:
1.
Completely define the layout of the split flue system, including accessories and outlet terminals.
2.
Consult "Table 8 - Accessories" and identify the losses in meq (equivalent metres) of each component based on the installation position.
3.
Check that the total sum of the losses is less than or equal to the maximum length allowed in "Table 7 - Maximum length of separate pipes".
Table 7 - Maximum length of separate pipes
Maximum length allowed
70 m
eq
Table 8 - Accessories
Losses in m
eq
Air extraction
Fumes exhaust
Vertical
Horizontal
Ø 80
PIPE
1 m M/F
1KWMA83W
1.0
1.6
2.0
BEND
45° M/F
1KWMA65W
1.2
1.8
90° M/F
1KWMA01W
1.5
2.0
PIPE JOINT
with test port
1KWMA70W
0.3
0.3
TERMINAL
air wall-mounted
1KWMA85A
2.0
-
fumes wall-mounted with wind
cowl
1KWMA86A
-
5.0
FLUE
Split air/fumes 80/80
010027X0
-
12.0
Fumes only outlet Ø80
01
4.0
1KWMA86U
Ø 60
PIPE
1 m M/F
1KWMA89W
6.0
BEND
90° M/F
1KWMA88W
4.5
REDUCTION
80/60
041050X0
5.0
TERMINAL
fumes wall-mounted with wind
cowl
1KWMA90A
7.0
Ø 50
PIPE
1 m M/F
041086X0
12
BEND
90° M/F
041085X0
9
REDUCTION
80/50
041087X0
10
CAUTION
GIVEN THE HIGH LOAD LOSSES OF THE ACCESSORIES Ø50 and Ø60, ONLY USE THEM IF NECESSARY AND IN LINE
WITH THE FINAL FUMES EXHAUST SECTION.