19
EN
Cod. 3542B230 - Rev. 00 - 02/2022
OMNIA S HYBRID H 3.2
3. TECHNICAL DATA AN PERFORMANCE
3.1 Heat pump technical data
-
Models
4
6
8
10
UM
A7W35
Thermal power
nom
4.20
6.35
8.40
10.0
kW
Power absorbed
nom
0.82
1.28
1.63
2.02
kW
COP
5.10
4.95
5.15
4.95
W/W
Water flow rate
722
1092
1445
1720
l/h
External static pressure
81
76
61
47
kPa
A7W45
Heating capacity
nom
4.30
6.30
8.30
10.0
kW
Power absorbed
nom
1.13
1.70
2.16
2.67
kW
COP
3.80
3.70
3.85
3.75
W/W
Water flow rate
740
1084
1428
1720
l/h
External static pressure
81
76
62
47
kPa
A7W55
Heating capacity
nom
4.40
6.00
7.50
9.50
kW
Power absorbed
nom
1.49
2.03
2.36
3.06
kW
COP
2.95
2.95
3.18
3.10
W/W
Water flow rate
473
645
806
1021
l/h
External static pressure
83
81
80
77
kPa
A35W18
Cooling capacity
nom
4.50
6.50
8.30
9.90
kW
Power absorbed
nom
0.82
1.35
1.64
2.18
kW
EER
5.50
4.80
5.05
4.55
W/W
Water flow rate
774
1118
1428
1703
l/h
External static pressure
80
75
62
48
kPa
A35W7
Cooling capacity
nom
4.70
6.50
7.45
8.20
kW
Water flow rate
nom
1.36
2.17
2.22
2.52
kW
EER
3.45
3.00
3.35
3.25
W/W
Water flow rate
808
1118
1281
1410
l/h
External static pressure
80
75
68
63
kPa
The values refer to a unit without any optionals or accessories.
Data declared according to EN 14511:
EER (Energy Efficiency Ratio) = ratio of the total cooling capacity to the effective power input of the unit
COP (Coefficient Of Performance) = ratio of the total heating capacity to the effective power input of the unit
A7W35 = source: air in 7°C d.b. 6°C w.b. / system: water in 30°C out 35°C
A7W45 = source: air in 7°C d.b. 6°C w.b. / system: water in 40°C out 45°C
A7W55 = source: air in 7°C d.b. 6°C w.b. / system: water in 47°C out 55°C
A35W18 = source: air in 35°C d.b. / system: water in 23°C out 18°C
A35W7 = source: air in 35°C d.b. / system: water in 12°C out 7°C
Outdoor unit technical data
4
6
8
10
UM
Power supply
220/240-1-50
V-ph-Hz
Type of compressor
Twin Rotary DC
-
No. compressors / No. refrigeration circuits
1 / 1
no.
Exchanger type
finned coil
-
Fan type
DC axial
-
No. of fans
1
no.
Refrigerant fittings / liquid line
1/4” SAE / Ø 6.35
3/8” SAE / Ø 9.52
-
Refrigerant fittings / gas line
5/8” SAE / Ø 15.88
-
Type of refrigerant
R32
type
GWP
675
kg-
CO
2
eq.
Factory refrigerant charge *
1.5 / 1.01
1.65 / 1.11
kg /
t-
CO
2
eq.
Refrigeration lines (max length / max
vertical height difference)
30 / 20
m
SWL - Sound power
level in heating **
A7W35
55
57
59
60
dB(A)
A7W55
56
58
59
60
dB(A)
Max
60
61
61
62
dB(A)
Sil. 1
56
56
57
58
dB(A)
Sil. 2
53
53
55
55
dB(A)
SWL - Sound power
level in cooling
*
A35W18
56
58
59
60
dB(A)
A35W7
56
58
59
60
dB(A)
Max
60
61
61
62
dB(A)
Sil. 1
55
57
57
58
dB(A)
Sil. 2
52
54
54
54
dB(A)
Maximum input current
12
14
16
17
A
Net weight
58
77
kg
Weight of packaged unit
65
94
kg
* The factory refrigerant charge allows a maximum length of the refrigeration lines of 15 metres. The maximum length of the refrigeration lines is 30 meters: in this case it is necessary to integrate the charge during
installation.
**: SWL =
Sound power levels, with reference to 1x10-12 W with unit operating in conditions:
A7W35
= source: air in 7°C d.b. 6°C w.b. / system: water in 30°C out 35°C.
A7W55
= source: air in 7°C d.b. 6°C w.b. / system: water in 47°C out 55°C.
A35W18
= source: air in 35°C d.b. / system: water in 23°C out 18°C
A35W7
= source: air in 35°C d.b. / system: water in 12°C out 7°C
Max
= at maximum conditions in heating / cooling mode
Sil. 1
= if silent level 1 active in heating / cooling mode
Sil. 2
= if silent level 2 active in heating / cooling mode
The Total sound power level in dB(A) is measured in accordance with standard ISO 9614.