Error code
Unit
in error
Malfunction or protection
Cause of fault and corrective action
Hd
IU
Communications error between the hydronic
boards (for cascaded applications)
1.The signal cables of the slave and master units are not correctly connected. After checking that all
the signal cables are securely connected and ensuring that there are no strong magnetic interfer-
ences, switch on again;
2. There are two or more hydronic boards connected to the user interface. Keep only one user inter-
face connected to the master unit and then, switch on again;
3. The start delay between the master and slave units is greater than 2 minutes. After ensuring that
the interval between the start-up of the master unit and slave unit is less than 2 min, switch on again;
4. Conflict between the master and slave unit addresses:
When you press the SW2 button on the main slave unit board, the address code of the slave unit is
displayed (the code used normally goes from 1, 2, 3 ... to 15); check if a there is a duplicated address.
If there is a duplicated address, after switching off the system, set S4-1 to “ON” on the control unit
hydronic board and on the hydronic board which displays the “Hd” error. Switch on all the units again,
wait 5 minutes without the “Hd” error, switch off again and set S4-1 to “OFF”. The system will be reset.
HE
IU
Communications error between the main board
and the thermostat expansion board
The RT/Ta board is correctly configured on the user interface, but the thermostat expansion board
is not connected or the communication between the board and the hydronic board is interrupted.
HF
EU
Eprom EE error on the inverter module board 1. EEprom error; rewrite the data on the EEprom.
2. The EEprom is faulty; replace it with a new one.
3. The inverter module board is broken; replace it with a new one.
HH
EU
H6 displayed 10 times in 2 hours
Refer to H6
HP
EU
Low pressure protection in cooling Pe<0.6 oc-
curred 3 times in one hour
Refer to P0
L0
EU
Inverter module protection
-
L1
EU
Protection for low voltage on DC bus
-
L2
EU
Protection for high voltage on DC bus
-
L4
EU
MCE error
-
L5
EU
Zero speed protection
-
L7
EU
Phase sequence error
-
L8
EU
Frequency variation of the compressor greater
than 15Hz per second
-
L9
EU
Working frequency of the compressor different
over 15Hz compared to target frequency.
-
P0
EU
Low pressure switch protection
1. The system has no refrigerant. Look for the leak, repair it and fill with the correct load.
2. The water flow is too low in cooling mode. Increase the water flow.
4. The electric expansion valve is blocked or the power supply has come loose. Try to release the
valve by gently tapping it. Connect/disconnect the connector multiple times to ensure that the valve
is working correctly.
P1
EU
High pressure switch intervention
-
P3
EU
Compressor electrical current absorption great-
er than maximum limit allowed
-
P4
EU
Compressor drain temperature (Tp) greater
than the maximum limit allowed
-
P5
IU
Temperature difference between Tw_out and
Tw_in too high
1. Make sure that all the shut-off valves in the water circuit are completely open.
2. Check if the water filter need cleaning.
3. Make sure there is no air in the system (bleed the air).
4. Check the water pressure. The water pressure must be > 1 bar
5. Check that the pump speed setting is on the maximum speed.
6.Make sure that the expansion vessel is not broken.
7. Check that the resistance in the water circuit is not too high for the pump.
P6
EU
Inverter module protection
-
Pb
IU
Antifreeze protection
The unit will automatically return to normal operation.
Pd
EU
Coil probe temperature (T3) greater than maxi-
mum limit allowed in cool mode
-
PP
IU
Error due to difference in temperature between
Twout and Twin not in line with the operating
mode. The error appears in heat mode if Twout
is less than Twin for more than 15 minutes
1.Check the resistance of the 2 temperature probes.
2.Check the position of the 2 probes.
3.The probe connector is disconnected. Reconnect it.
4.One or both probes are faulty; replace them.
5.The four-way valve is blocked. Restart the unit to allow the valve to be released.
6.The four-way valve is broken; replace it.