9. GENERAL USER MENU
To access the user menu, press the button. To scroll the rows using the SW1 and SW2 buttons to access the submenu, press the button. The menu is structured
in multiple levels as shown in the following table.
Level 1
Level 2
Description
Lower limit
Upper
limit
Remedy Unit of measure-
ment
Default
value
System
Plant type *
Select the heat pump system type (Elec-
tric, Hybrid C, Hybrid H)
Electric
Hybrid H
Hybrid H
Functional pref. *
To select the functional preference
Comfort
Efficiency
Comfort
Hp menu
See "9.3.1 User heat pump menu
(hp menu)"
you enter the heat pump menu
Boiler menu
See "9.2 Boiler menu"
you enter the boiler menu
BMS menu
Device address
communications port settings for BMS
1
247
1
Bitrate
9600
38400
Baud rate
9600
Parity
None-Even-Odd
None
Stop bit
1
2
1
*: Do not modify
9.1 System menu
9.1.1 Functional preference
It is possible to select the functional preference that can be set, Efficiency or Comfort, from the system menu.
Efficiency functional preference
Heating mode
• The heat pump and boiler operate in heating mode based on the parameters set with the goal of maximising the system energy efficiency.
DHW mode
• The request for filling the DHW tank is fulfilled by giving priority to heat pump operation and activating the boiler to supplement or replace the heat pump based on
the parameters set.
Comfort functional preference
Heating mode
• The heat pump and boiler operate in heating mode based on the parameters set with the goal of maximising the system energy efficiency.
DHW mode
• If the heat pump is supporting the system in heating or cooling mode, the request to fill the DHW heater is fulfilled by the boiler while the heat pump continues to
serve the system.
• If the heat pump is not supporting the system in heating or cooling mode, the request for filling the DHW tank is fulfilled by giving priority to heat pump operation and
activating the boiler to supplement or replace the heat pump based on the parameters set.
9.2 Boiler menu
9.2.1 User boiler menu
Press the button to access the boiler menu and select the line “Boiler menu”. The menu is structured in multiple levels as shown in the following table.
Level 1
Level 2
Level 3
Level 4
Description
Lower
limit
Upper
limit
Remedy
Unit
of meas-
urement
Default
value
Service
"Password”
1234
TSP, see “Menu
for modifying the
[TSP] param-
eters" on page
52
b01 - P68
boiler parameters
Test
b01 - P69
AutoSetip
Diagnostic
CH1 temp
delivery probe temperature
0
125
1
°C
CH2 temp
return probe temperature
0
125
1
°C
DHW temp
DHW temperature
0
125
1
°C
Ext temp
external temperature
-30
70
1
°C
Fume temp
temperature of fumes
0
125
1
°C
Fan speed
Fan speed
0
120
100
rpm
Pump speed
Circulator speed
0
100
1
%
Power
Burner power
0
100
1
%
DHW flow
DHW flow
0
99
0.1
l/min
Water pressure
System water pressure
0
9.9
0.1
bar
Flame
Flame signal
0
255
1