XL-4, XL-4B, and XL-5 LCD Keypad Programming Manual
Version 4
8–20
CS#1 & CS#2
Both receivers always
CS#1 BU CS#2
CS#1 backed up by CS#2
CS#2 BU CS#1
CS#2 backed up by CS#1
NONE
No Test transmissions
Press the 0 key to toggle through the available choices.
UL
Test code transmission shall be enabled in UL Listed applications.
System Test Interval
037 TEST FREQ
24 HOUR
Indicates the frequency of automatic system test reports. Test reports can be transmitted to
the Central Station on a daily (every 12 or 24 hours) or on a weekly basis. System Test
signals will be transmitted only if a transmission path is specified in question 036. The test
code transmitted,depending on the format selected, is entered in System Test questions
(#092 and #93). The time of day (hour and minute) for transmission of system test is entered
in questions 038 & 039. Press 0 to toggle between the following options:
12 HOUR
24 HOUR
SUNDAY
MONDAY
TUESDAY
WEDNESDAY
THURSDAY
FRIDAY
SATURDAY
System test will report the account number for partition #1 in a multi-partitioned system.
UL
The test frequency shall be 12 or 24 hours for UL listed applications.
Test Time - Hour
038 TEST TIME HR
23 (00 - 23)
Enter the hour of the day, in 24-hour time, for transmission of system test signal. For
example, 5PM = 17. The test time is only applicable if there is a test signal and transmission
path defined.
Summary of Contents for XL-4
Page 1: ...N9145V2 10 98 6HFXULW 6 VWHP 3URJUDPPLQJ XLGH 9HUVLRQ...
Page 6: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 1 2...
Page 12: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 2 6...
Page 14: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 3 2...
Page 18: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 5 2...
Page 88: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 8 66...