Section 8 - LCD Keypad Programming Questions
8–3
Primary Central Station Receiver
003 CS1 PH. #
234
The system can transmit digital alarm signals to two separate Central Station numbers.
Enter the complete telephone number of the primary Central Station receiver line. The
telephone number should be entered with the correct area code or access control digits
necessary to dial the Central Station receiver from the panel location.
The primary CS receiver (CS#1) telephone number can contain up to 32 digits. If the panel
does not communicate with the primary Central Station or the panel is being used in a local
only application (see question 016) then leave this question blank.
To erase an entire existing telephone number, position the cursor at the first digit and
depress the SHIFT key (
✴
) followed by the 8 key.
See the Callback Number for a full explanation of telephone number entry.
CS#1 Receiver Type
004 TYPE CS1
FBI SUPER 2300HZ
The control panel transmits in a variety of DTMF and pulse formats to the Central Station
receiver. This question selects the type of CS transmission made to CS#1. The valid options
are:
FBI SUPER 1400HZ
FBI Superfast Format 1400 HZ Handshake
FBI SUPER 2300HZ
FBI Superfast Format 2300 HZ Handshake
ADEMCO Point ID
ADEMCO Point ID format
4x2 Express
ADEMCO 4x2 Express format
BFSK 2300
RADIONICS BFSK 2300HZ handshake
10P 1400 STAND
10 Pulses Per Second, 1400 Hz handshake, Standard Format
10P 2300 STAND
10 Pulses Per Second, 2300 Hz handshake, Standard Format
10P 1400 ACC+2
10 Pulses Per Second, 1400 Hz handshake, 3x2 or 4x2 Format
10P 2300 ACC+2
10 Pulses Per Second, 2300 Hz handshake, 3x2 or 4x2 Format
10P 1400 EXTEND
10 Pulses Per Second, 1400 Hz handshake, Extended Format
10P 2300 EXTEND
10 Pulses Per Second, 2300 Hz handshake, Extended Format
10P 1400 PART EX
10 Pulses Per Second, 1400 Hz handshake, Partial Extended
10P 2300 PART EX
10 Pulses Per Second, 2300 Hz handshake, Partial Extended
20P 1400 STAND
20 Pulses Per Second, 1400 Hz handshake, Standard Format
20P 2300 STAND
20 Pulses Per Second, 2300 Hz handshake, Standard Format
20P 1400 ACC+2
20 Pulses Per Second, 1400 Hz handshake, 3x2 or 4x2 Format
20P 2300 ACC+2
20 Pulses Per Second, 2300 Hz handshake, 3x2 or 4x2 Format
20P 1400 EXTEND
20 Pulses Per Second, 1400 Hz handshake, Extended Format
20P 2300 EXTEND
20 Pulses Per Second, 2300 Hz handshake, Extended Format
20P 1400 PART EX
20 Pulses Per Second, 1400 Hz handshake, Partial Extended
20P 2300 PART EX
20 Pulses Per Second, 2300 Hz handshake, Partial Extended
40P 1400 STAND
40 Pulses Per Second, 1400 Hz handshake, Standard Format
40P 2300 STAND
40 Pulses Per Second, 2300 Hz handshake, Standard Format
40P 1400 ACC+2
40 Pulses Per Second, 1400 Hz handshake, 3x2 or 4x2 Format
40P 2300 ACC+2
40 Pulses Per Second, 2300 Hz handshake, 3x2 or 4x2 Format
40P 1400 EXTEND
40 Pulses Per Second, 1400 Hz handshake, Extended Format
40P 2300 EXTEND
40 Pulses Per Second, 2300 Hz handshake, Extended Format
Summary of Contents for XL-4
Page 1: ...N9145V2 10 98 6HFXULW 6 VWHP 3URJUDPPLQJ XLGH 9HUVLRQ...
Page 6: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 1 2...
Page 12: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 2 6...
Page 14: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 3 2...
Page 18: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 5 2...
Page 88: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 8 66...