Section 8 - LCD Keypad Programming Questions

8–13

Remote Disarm Enable

018 REM DISARM
YES

Indicates whether this panel can be disarmed remotely through the EZ-MATE PC Based
Downloader. This question provides an additional layer of security for remote operations.
This question will be skipped if the answer to the Remote Operations question 17 is NO. If
the system is programmed for transmission of closing signals then the signal will be sent
after completion of the downloading session.

UL

This question must be answered "NO" for UL listed systems.

Remote Arm Enable

019 REM ARM
YES

Indicates whether this panel can be armed remotely through the EZ-MATE PC Based
Downloader. This question provides an additional layer of security for remote operations.
This question will be skipped if the answer to the Remote Operations question 17 is NO. If
the system is programmed for transmission of opening signals then the signal will be sent
after completion of the downloading session.

Remote Bypass Enable

020 REM BYPASS
NO

Indicates whether this panel can have individual zones bypassed or unbypassed remotely
through the EZ-MATE PC Based Downloader. This question will be skipped if the answer to
the Remote Operations question 17 is NO. If the system is programmed for transmission of
bypass signals, then the signal will be sent after completion of the downloading session.

UL

This question must be answered "NO" for UL listed systems.

Number Of Attempts

021 # ATTEMPTS
08   (01-16)

Indicates the number of attempts made by the dialer to reach the Central Station receiver.
Transmission will repeat up until the maximum number of attempts if a transmission is
unsuccessful.

If the Central Station reporting path transmits signals to either receiver telephone numbers
then transmission will alternate between the two numbers if either line is busy.

Default value = 08, 16 means 16 attempts.

UL

For UL Listed applications this shall be programmed for a value between 5 and 10 attempts.

Summary of Contents for XL-4

Page 1: ...N9145V2 10 98 6HFXULW 6 VWHP 3URJUDPPLQJ XLGH 9HUVLRQ...

Page 2: ...ction 8 LCD Keypad Programming Questions 8 1 General 8 1 CS Communications 8 1 User Definition 8 14 System Attributes 8 17 System Timing 8 28 System Function Codes 8 32 Alarm Types 8 37 Trouble Types...

Page 3: ...otes include information that you should be aware of before continuing with the installation and which if not observed could result in operational difficulties This symbol indicates a critical note th...

Page 4: ...tition Question 34 Even zones can be defined as tampers for odd zones If selected all even zones will report a tamper in the partition that the previous odd zone was enabled in Question 83 A common pa...

Page 5: ...pad display These displays contain easy to understand simple English language prompts The programming questions are described in detail in the LCD Keypad Programming Questions section of this manual K...

Page 6: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 1 2...

Page 7: ...ogram can be thought of as simply modifying the defaults There are numerous programming options but for standard applications only a few of them need to be changed For example to modify the system to...

Page 8: ...hat zone Similarly an alarm can occur only when the panel is armed unless 24 Hour Alarm is enabled for that zone In addition a zone can be connected without the EOL resistor by simply selecting its pa...

Page 9: ...pening Closing signals to the CS by partition programming question 029 Once enabled the user s functions arming disarming bypass etc in the partition depends on its AUTHORIZATION LEVEL programming que...

Page 10: ...and user 004 USER 005 can modify itself and users 004 and 006 PARTITION 3 USER 001 is a master user and can modify itself and users 002 005 and 006 USER 003 can modify itself and users 004 005 and 00...

Page 11: ...the main entrance and into office 2 to disarm the system the disarming of partition 2 will also disarm partition 8 and partition 1 will remain in an armed state When the first user exits the building...

Page 12: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 2 6...

Page 13: ...or entry to installer functions such as keypad programming 1 The digit 1 on the keypad During keypad programming the function keys perform different functions See section 4 of this manual for further...

Page 14: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 3 2...

Page 15: ...UESTION key will sequence the display backward to the previous question of the programming sequence This key can be used scroll backwards through the questions FORWARD INSTANT KEY Advances the cursor...

Page 16: ...h the following A Z space 0 1 2 3 4 5 6 7 8 9 Alphabetic characters can be entered as lower case or upper case values ERASE FLD 8 KEY The ERASE FIELD function is performed by depressing the SHIFT key...

Page 17: ...ibe the question being asked Due to space limitations some question titles are abbreviated If the question deals with an area containing multiple offsets such as zones or users then the display will c...

Page 18: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 5 2...

Page 19: ...ial order without changing any of the current values The questions presented will depend on the Installer Programming level and the values in previous questions FORMAT NEXT Q NEXT Q NEXT Q Direct Meth...

Page 20: ...obtained At this point the contents of this field can be modified or another question can be obtained If the question requested belongs to an area that contains multiple offsets then the direct acces...

Page 21: ...ting codes and characteristics for different alarm conditions When setting up a zone an alarm type will be necessary The system contains up to sixteen alarm types TROUBLE TYPES Questions 129 141 Troub...

Page 22: ...P PARAMETERS Questions 184 194 One feature of the system is the capability to transmit a log of system activity to a local or remote serial printer These questions define the frequency of this transmi...

Page 23: ...ystem can be programmed and operated remotely from the Alarm Company location This optional two way capability includes remote programming uploading downloading and remote commands All remote activati...

Page 24: ...only sixteen characters a secondary display will automatically appear if a phone number greater than 16 characters is entered This secondary display will be denoted with a small left arrow in the las...

Page 25: ...0 Pulses Per Second 1400 Hz handshake Standard Format 10P 2300 STAND 10 Pulses Per Second 2300 Hz handshake Standard Format 10P 1400 ACC 2 10 Pulses Per Second 1400 Hz handshake 3x2 or 4x2 Format 10P...

Page 26: ...tion of the codes can be located in the appropriate questions within this manual Consult your Central Station manager to determine the formats acceptable to your Central Station Point ID PID Format Th...

Page 27: ...ccount number 3 or 4 digits event code parity bit if selected repeats the 3 or 4 digit account number and repeats the event code The second line repeats the event code equal to the number of digits in...

Page 28: ...ogrammed 3 digit user CS code from question 27 Zone Bypass Dedicated Code not programmable sends 570 Zone Bypassed Reports programmed 3 digit user CS code from question 145 Fire Bypass Dedicated Code...

Page 29: ...Trouble for Fire Zones sends 370 Protection Loop for Burg Zones Reports programmed 3 digit in Zone CS Code from question 145 Zone Restores Dedicated Code not programmable sends 3 Restore as Event Type...

Page 30: ...CS Code program as 000 015 reports as 0 F System Error Quest 131 System Error Trouble Type CS Code program as 0 F Quest 096 System Error CS Code program as 000 015 reports as 0 F Download Quest 097 Do...

Page 31: ...e not transmitted to CS 1 question 003 Sescoa Format CS 1 007 SESCOA NO This question indicates whether the Sescoa format for fixed digit timing will be transmitted to CS 1 Depression of the 0 key wil...

Page 32: ...0 Pulses Per Second 2300 Hz handshake Partial Extended 20P 1400 STAND 20 Pulses Per Second 1400 Hz handshake Standard Format 20P 2300 STAND 20 Pulses Per Second 2300 Hz handshake Standard Format 20P 1...

Page 33: ...stion 008 Sescoa Format CS 2 012 SESCOA NO This question indicates whether the Sescoa format for fixed digit timing will be transmitted to CS 2 NOTE This only applies to the various pulse based CS tra...

Page 34: ...all the telephone numbers are blank Dial Tone Detection 015 DIAL TONE NO Indicates whether the control panel will look for dial tone before attempting any dialing attempt If dial tone detection is sel...

Page 35: ...of opening signals then the signal will be sent after completion of the downloading session Remote Bypass Enable 020 REM BYPASS NO Indicates whether this panel can have individual zones bypassed or u...

Page 36: ...ains an anti jam feature before it performs any communicator dialing The anti jam feature will disconnect the internal telephone line and perform a hang up on any external connection The standard hang...

Page 37: ...Assignments in ALL partitions LEVEL 2 Arm Disarm Bypass Program Users and Change Partition Assignments in own partitions LEVEL 3 Arm Disarm Bypass and Program Users LEVEL 4 Arm Disarm and Bypass LEVEL...

Page 38: ...E 0 key allows YES NO selection for the partition For example the first position represents partition 1 the second position is partition 2 etc If using the common partition feature user codes should o...

Page 39: ...n the XL 5 The system contains 8 hardwired zones plus up to 64 multiplex points XL 4 and XL 4B or 120 multiplex points XL 5 using a two wire multiplex bus The multiplex zones are known as 9 72 XL 4 an...

Page 40: ...ly CS 1 CS 2 Both receivers always CS 1 BU CS 2 CS 1 backed up by CS 2 CS 2 BU CS 1 CS 2 backed up by CS 1 NONE No O C transmissions Press the 0 key to toggle through the available choices The opening...

Page 41: ...w meaning that the time is disabled and there will be no auto arm for that day 9 Re enter the programming mode to continue programming Clock Set Reporting Path 035 CLOCK PATH NONE Specifies the transm...

Page 42: ...nly if a transmission path is specified in question 036 The test code transmitted depending on the format selected is entered in System Test questions 092 and 93 The time of day hour and minute for tr...

Page 43: ...Path 041 BYPASS PATH NONE Specifies the Central Station transmission path for system bypasses The options are CS 1 ONLY Primary rec only CS 2 ONLY Secondary rec only CS 1 CS 2 Both receivers always C...

Page 44: ...resent UL This must be programmed YES in UL Listed systems Press the 0 key to toggle between the available choices Arming Output Level 045 ARM OUT LEV HIGH Indicates the desired voltage level on trigg...

Page 45: ...tes whether relay number 2 will be used as a fire or smoke reset for the hardwired zones of the system If YES then relay 2 will be dedicated to the fire reset function If Fire Verification is not used...

Page 46: ...hing NO ABORT No abort capability send alarm code RESTORE Transmit the restore code instead of the alarm code Press the 0 key to toggle between the available choices The abort action is system wide an...

Page 47: ...d then it will be available throughout all partitions of a multi partitioned system Quick forced arming will transmit the CLOSE signal if programmed for CS transmission along with the first user code...

Page 48: ...and off 6 will be available to users of the system If chime control is enabled then it will be available throughout all partitions of a multi partitioned system Each zone has an individual option to s...

Page 49: ...tiating a system default To obtain default lockout protection answer NO to this question If the Default Lockout option is selected then a system default will reset all of the programmable options exce...

Page 50: ...xample 00 No delay 03 45 second delay Each alarm type has a programmable option question 112 indicating whether the alarm type adheres to bell delay This allows certain emergency conditions to bypass...

Page 51: ...e see question 165 Specify entry delay 1 in 15 second increments The entry delay can be defined from 0 to 14 fifteen second intervals with 15 indicating an infinite exit delay UL In UL residential app...

Page 52: ...TRG NNNNNNNN Indicates whether any of the eight programmable voltage level output triggers will be activated upon an entrance condition The position of the Y or N indicates the trigger number This tri...

Page 53: ...ut feature merely prevents repeating activity from triggering the bell Signals will continue to be transmitted to the Central Station in accordance with the zone definition If signals are to be suppre...

Page 54: ...es that have been defined with lockout enabled If multiplex capability is present then the local lockout counter will be used to determine the number of bus supervision faults that will lock out the d...

Page 55: ...ypass restore An option exists per zone to determine whether bypasses are reported Bypasses will be reported to the Central Station based on the bypass option selected in question 167 If transmitting...

Page 56: ...change is performed at the keypad This signal will be transmitted based on the reporting path defined in question 035 If PID Format is selected then an event code of 625 will be transmitted Cancel Cod...

Page 57: ...at selected is Point ID PID then this defines the zone identification number to be transmitted to the CS If PID Format is selected then an event code of 301 will be transmitted If a 4x2 or extended fo...

Page 58: ...ding Software If PID Format is selected then an event code of 306 is transmitted If the Extended Partial Extended or 4 X 2 format is selected this will be the second digit transmitted following the do...

Page 59: ...goes into an alarm condition Each zone definition specifies an alarm type The alarm type includes information such as the description CS reporting code reporting type and trigger outputs For example t...

Page 60: ...ned in question 176 Alarm Type CS Code 110 CS CODE ATxx _ 0 F Indicates the code transmitted to the Central Station for this Alarm type The placement of the code in the transmission depends on the for...

Page 61: ...16 of the zone CS code question 145 Point ID Format Within the point ID format the alarm type CS code will not be utilized All alarm signals will be sent with the new condition indication See format e...

Page 62: ...active for this alarm type If the condition should be silent at the keypad then enter NO If the system is partitioned then this question will relate to all of the keypads defined within that partition...

Page 63: ...d 8 must be set to N if the XL 4705 relay module is used Alarm Type Latched Triggers 120 LAT TRG ATxx NNNNNNNN Indicates which of the voltage level triggers will be activated for a maintained duration...

Page 64: ...ic alarm type and the timeout selected will be used for both relays UL For UL Listed systems this option shall be programmed NONE External Relay Address 1 123 XTRIG 1 ATxx xx 00 40 Selects a relay in...

Page 65: ...RWARD INSTANT and BACKWARD CODE keys will move the cursor position to the desired trigger position which indicates the trigger number The TOGGLE 0 key will change the Yes No status of the trigger Afte...

Page 66: ...xt sequential Trouble Type as the selected value Trouble Type Description 130 DESCR TR x __________ The Trouble Type descriptions are used to provide English language text on the first line of the LCD...

Page 67: ...3 T TTT Z where T Trouble type CS Code and Z is the CS code contained in the zone definition question 145 This format can contain either three or four digits within the account number PARTIAL EXTENDED...

Page 68: ...gle between the available choices NOTE For UL Listed systems this must not be programmed as NONE Trouble Type Dialer Delay 134 DIAL DL TR x YES Indicates whether the dialer delay specified in the Syst...

Page 69: ...Latched Triggers 139 LAT TRG TR x NNNNNNNN Indicates which of the voltage level triggers will be activated for a maintained duration with this Alarm Type The triggers are selected by placing a Y in th...

Page 70: ...l 7120 or 7126 The zones are numbered as follows TOTAL ZONES EXPANSION MODULE XL 4 XL 4B AND XL 5 BASIC HARDWIRED ZONES XL 4 AND XL 4B EXPANSION ZONES XL 5 EXPANSION ZONES 8 NONE 1 8 NONE NONE 16 7105...

Page 71: ...e panel is reset the respective zones will be identified as missing As a result multiplex zones are fully supervised by this method This method should always be selected Select Zone Number 142 SEL ZON...

Page 72: ...uestions 004 and 009 Enter the desired zone code from 000 255 If the desired code to be transmitted to the Central Station should be a hex code then that code must be entered in decimal as follows A 0...

Page 73: ...where A Alarm type CS Code question 110 and Z is the zone CS code If the condition will initiate a trouble signal then the A will originate from the Trouble Type entered in question 131 NOTE This for...

Page 74: ...on 153 Loss of Heat 154 Water Leakage 155 Foil Break 156 Day Trouble 157 Low Bottled Gas Level 158 High Temperature 159 Low Temperature 161 Air Flow Loss SUPERVISORY 200 Fire Supervisory 201 Low H2O P...

Page 75: ...be used for interior zones to have selected zones bypassed while remaining in the location Press the 0 key to toggle between the available choices This location should be programmed NO for fire zones...

Page 76: ...types Group bypasses can be performed through the command BYPASS USER 1 GRP where GRP is the group number 01 24 Group unbypasses can be performed through the command BYPASS USER 2 GRP where GRP is the...

Page 77: ...t identifies a restore by the zone number and type of alarm STANDARD Example 123 R where R Restore code defined for the alarm type of this zone question 111 The value entered for the Zone CS code ques...

Page 78: ...a day regardless of the arming status of the panel This question should be answered YES for either a keyswitch smoke detector or other fire circuits UL For UL Listed systems fire zones must be progra...

Page 79: ...sing characteristics of the device connected to this zone For example this should be answered as YES for a keyswitch and NO for a smoke detector UL For UL Listed systems fire zones shall be NO Press t...

Page 80: ...of the exit delays is defined in questions 69 70 This question is only used if the zone type is an Exit Entry or Interior EE follower Zone Entry Delay 165 ENT DEL Zxxx DELAY 1 Specifies which of the s...

Page 81: ...time the zone is faulted This will occur only when the system is disarmed Press the 0 key to toggle through the available choices Zone 750ms Response HW Zones Only 170 EN 750M Zxxx YES Indicates whet...

Page 82: ...nitiated conditions will react as defined within this section based on the partition assignment of the keypad where the condition is activated The keypad conditions can be initiated as follows CONDITI...

Page 83: ...S REST KP x YES Indicates whether the keypad condition will send a restore code to the central station If enabled a restore code will accompany the event code Partitions This section of the Installer...

Page 84: ...P _ ____ Enter the account number to be reported to CS 1 Question 3 The portion of the display labeled P indicates the partition number being entered The account numbers can be up to four digits If a...

Page 85: ...ure is in addition to any signals transmitted to the Central Station The Auto Dump feature will transmit the system log information to a remote printer located at the DUMP phone number see question 00...

Page 86: ...ed for the desired day of the week for transmission The TOGGLE 0 key will scroll through the days of the week from Sunday through Saturday Hour Of Day 187 REPORT HOUR 00 00 23 Enter the desired hour i...

Page 87: ...that is transmitted Provision is made for the entry of four lines of comments to be transmitted as a heading for each printout This description should be used to identify the account at the remote pri...

Page 88: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 8 66...

Page 89: ...ypass NO 021 Attempts 08 022 of Rings to Pickup 08 023 Extended Antijam NO 024 Extended Acknowledge NO User Attributes 025 Select User Number 001 064 025 027 026 030 028 029 User Access User User Auth...

Page 90: ...back at Closing NO 048 Sounder Ringback Enable YES 049 Fire Reset Verification YES 050 Enable Reset Key Function NO 051 En Rest to Follow Loop NO 052 Action on Abort NO ABORT 053 En Multi Part Mode YE...

Page 91: ...Triggers NONE on all 120 Latched Triggers NONE on all 121 Relay 1 Select P L L L N N N N N 122 Relay 2 Select N N N N N N N N N 123 Ext Relay Address 1 01 05 09 13 17 21 25 29 33 124 Ext Relay Addres...

Page 92: ...E 13 14 INSTANT ZONE 14 15 INSTANT ZONE 15 16 INSTANT ZONE 16 17 INSTANT ZONE 17 18 INSTANT ZONE 18 19 INSTANT ZONE 19 20 INSTANT ZONE 20 21 INSTANT ZONE 21 22 INSTANT ZONE 22 23 INSTANT ZONE 23 24 IN...

Page 93: ...ore YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES 155 Partition Selection 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 156 24 Hour Alarm NO NO NO NO NO NO NO YES NO NO NO NO NO NO NO NO 157 24 Ho...

Page 94: ...FF FFFF N N N N N N N N N N N N N N N N NOTE Only LCD keypad 1 is enabled Therefore only a single LCD keypad addressed as keypad 1 should be connected for first time power up of the system Additional...

Page 95: ...nfirm Path 041 Bypass Transmission Path 042 Disable Bypass on Stay 043 Transmit Bypass on Arming 044 Auto Unbypass Enable 045 Arm Outputs Level 046 Bell Test At Arming 047 Bell Ringback at Closing 048...

Page 96: ...ulted 151 Force Arm Faulted 152 Group Enable 153 CS Trouble 154 CS Restore 155 Partition Selection 156 24 Hour Alarm 157 24 Hour Trouble 158 Alarm Type 159 Trouble Type 160 Alarm on Open 161 Alarm on...

Page 97: ...8 3 8 10 Remote Arm Enable 8 13 Remote Bypass Enable 8 13 Remote Disarm Enable 8 13 Remote Operation 8 12 Ring Count 8 14 Secondary Central Station Receiver 8 9 Sescoa Format 8 9 8 11 Display Format...

Page 98: ...Attributes 9 1 Zone Attributes 9 4 System Function Codes Programming 8 32 System Function Codes Programming 24 Hour AC Loss 8 36 8 37 24 Hour Low Battery 8 36 24 Hour System Error 8 37 Abort Code 8 3...

Page 99: ...Trouble 8 56 Zone Alarm On Open 8 57 Zone Alarm On Short 8 57 Zone Alarm On Trouble 8 57 Zone Alarm Type 8 57 Zone Buzzer On Trouble 8 59 Zone Bypass Enable 8 53 Zone Chime Enable 8 59 Zone CS Restor...

Page 100: ...1 9 Al N9145V2 10 98 Subsidiary of Pittway Corp 149 Eileen Way Syosset New York 11791 Copyright 1998 PITTWAY CORPORATION...

Reviews: