Press the 0 key to toggle through the available choices.
Zone Trouble On Short
163 TR SHRT Zxxx
NO
Indicates whether this zone activates a trouble condition on a short circuit. This question will
depend on the sensing characteristics of the device connected to this zone. For example, this
should be answered as NO for a smoke detector. Press the 0 key to toggle through the
available choices.
Zone Exit Delay
164 EXT DEL Zxxx
DELAY #1
Specifies which of the system exit delay times should be used for this zone. The TOGGLE (0)
key will switch between DELAY1 & DELAY2. The duration of the exit delays is defined in
questions 69 & 70.
This question is only used if the zone type is an Exit/Entry or Interior EE follower.
Zone Entry Delay
165 ENT DEL Zxxx
DELAY #1
Specifies which of the system entry delay times should be used for this zone. The TOGGLE
(0) key will switch between the two values. The duration of the delays is defined in questions
71 - 72.
This question is only used if the zone type is an Exit/Entry or Interior EE follower.
Zone Lockout Enable
166 EN LOCK Zxxx
YES
Indicates whether this zone participates in either bell or dialer lockout. If YES then the
various lockout information defined in questions 79 - 82 will be used for this particular zone.
UL
Lockouts shall be disabled in UL Listed applications.
CS Bypass
167 CS BYP Zxxx
NO
Indicates whether this zone will transmit a bypass code to the Central Station.
Summary of Contents for XL-4
Page 1: ...N9145V2 10 98 6HFXULW 6 VWHP 3URJUDPPLQJ XLGH 9HUVLRQ...
Page 6: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 1 2...
Page 12: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 2 6...
Page 14: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 3 2...
Page 18: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 5 2...
Page 88: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 8 66...