CALIBRATION (LIVE READOUT)
The Jackal also allows for a semi-automatic setup when the voltage values are unknown for a particular voltage
input. A live voltage readout is displayed in the top left-hand side when the sensor is active.
Follow the previous 5 steps, followed by:
Press
EDIT
to change the
unit. kPa,psi,bar,Volt,%,
˚
C.
i.e. kPa
Engage the implement
and/or adjust the pressure
manually to the low point the
sensor will need to operate
in.
The voltage will now be
displayed. e.g.
1.75v
.
In the above example we can
set the minimum of
1kPa
by
HIGHLIGHTING
&
EDITTING
the values as required.
Press
SET
. This will copy the
live voltage into the
CAL LOW
voltage point
Repeat the previous 2 steps
for the
CAL HIGH
values
Highlight or confirm the UOD
(Unit of Display)
e.g. kPa
Press
NEXT
when done
You have the option to set
Alarm Min/Max points if
required. Using the NAV
buttons select &
EDIT
as
required. Press
NEXT
Name the input if you desire,
Press
EDIT
or Press
NEXT
The Wizard is now complete.
Press
NEXT
You will be returned to the
front screen
THIS ENDS THE AUTO SETUP FOR A VARAIBLE VOLTAGE INPUT SENSOR (LIQUID)