Machine Setup
BYO PRESSURE & MANUAL SETUP
Select the Pressure Sensor number you wish to calibrate. Select Type as USER and then CALIBRATE.
Pressure Low: Input the lowest pressure the unit will need to display.
Voltage Low: You can either:
1.
Manually add the Voltage Low (as per manufacture specifications), or
2.
Adjust your pressure manually to the low point and then select SET VOLT. This will take the value
from the LIVE input voltage and automatically insert. (Refer to manual pressure gauge if fitted.)
Pressure High: Input the highest pressure the unit will need to display.
Voltage High: You can either:
1.
Manually add the Voltage High (as per manufacture specifications), or
2.
Adjust your pressure manually to the High point and select SET VOLT. This will take the value from
the input voltage and automatically insert. (Refer to manual pressure gauge if fitted.)