Lumina 35
Explanation control functions
4
Part of the ventilation demand can be met using natural ventilation. During natural ventilation the fans are off. The
outside wind provides the air flow through the house. The entire combi-table is deactivated in the natural
ventilation phase.
Outside the natural ventilation range, ventilation is controlled using the fans. The inlets are opened
based on the values in the combi-table.
Figure 2: Ventilation graph with transition phases
Transition Power ventilation → Natural ventilation (1)
At a rising temperature and when the
Natural start
(1) is reached, the control computer switches to natural
ventilation. To prevent toggling the system must have been out of the natural phase for a certain time before
system returns to the natural phase again. The control computer opens the curtain, then switches the fans off.
The control computer controls how far the curtains open based on the minimum natural inlet settings.
Transition Natural ventilation → Power-Tunnel ventilation (2)
If the temperature continues to rise the control computer switches over to mechanical ventilation when the air inlet
is fully opened (curtain opened to maximum) and the temperature rises above
Natural stop
(2). The inlets for
natural ventilation (curtains) are closed, if required. The inlets for mechanical ventilation are opened based on the
values in the combi-table. The required fans are activated.
Transition Power-
Tunnel ventilation → Natural ventilation (2)
With falling temperatures the control computer switches over to natural ventilation when the temperature falls
below the position
Natural stop
(2). The curtains are opened to maximum position. Then the fans are switched off.
To prevent toggling the system must have been out of the natural phase for a certain time before system returns
to the natural phase again.