Delay
Setting of the
Delay
to minimise the influence of temperature fluctuations.
The control computer only applies the OptiSec-correction, if the actual house
temperature has fallen below the setpoint house temperature during the wait time.
For example, set a wait time of 2 hours. The control computer will only increase the
correction when the actual house temperature has been below the setpoint house
temperature for an uninterrupted period of 2 hours. If the actual house temperature
briefly comes above the setpoint house temperature, the
Delay
will be reset.
The wait time also applies to the decrease of the corrections. The control computer will
only decrease the correction when the actual house temperature has been above the
setpoint house temperature for an uninterrupted period of 2 hours.
Slope time
Setting of the time within which the control computer must complete the required
correction increase or decrease.
Delay cnt
Readout of the already elapsed
Delay
(minutes).
Correction
Readout of the actual correction using OptiSec.
INSTALLER
→
HEAT COOL HUM
→
tab page
Cool
Description
Setting of the name of the function.
Temp. inputs
Setting the addresses of the analog inputs. If the temperature sensors have not been
assigned, the control computer will use the house temperature.
Control
Setting of the cooling control type:
LINEAR
or
RELAY
.
Output address
Setting of the analog output address (choice
LINEAR
control) or relay output (choice
RELAY
control).
Relay type
*
Setting of the type of relay control (
ON/OFF
/
Modulating
).
Evaporative cooling
Setting indicating if evaporative cooling is used (
YES
or
NO
).