Lumina 35
Installer
35
INSTALLER
→
VENTILATION
→
COMBI MTT
→
M/MT-phase (min)
→
tab page
Cap.
Position %
Setting of the ventilation percentage at which fans should activate/deactivate and air
inlets open/close. The ventilation percentages must increase from the lowest to the
highest position.
The combi positions are also used for natural ventilation.
Pressure Pa
Setting of the required pressure for the corresponding position. A rule of thumb: the
higher the ventilation position, the lower the required pressure. Enter 0 to deactivate
pressure control.
Cap m³/h
Setting of the ventilation capacity (m3/hour) for all positions used. If ventilation is used
in m3/hour/animal, always fill in this column!
INSTALLER
→
VENTILATION
→
SETTINGS
→
tab page
Miscell.
Combi control
Setting of the speed of progression to the next or previous position in the combi-table.
Choose from
SLOW
/
MODERATE
/
FAST
.
Select
SLOW
if the transitions follow too quickly in succession. If it takes too long before
the control computer proceeds to another position select
FAST
.
Delay MT->T
Setting of the delay for transition from MT- to T-position. During the set time the control
computer will not change the exhaust at this transition.
This delay does not apply with the transition from T to MT (direct control).
Actual combi step
Setting of the current phase in the combi-table.