Lumina 35
Technical specifications
54
FDP25
Mains voltage
90Vac
– 264Vac
Main frequency
50/60Hz
Maximum power consumption
25VA
IOB.4
Power available for sensors and peripheral equipment
24Vdc (short circuit resistant)
max. 500mA
12Vdc, short circuit resistant
max. 70mA
4x analog outputs (AO)
Voltage range
0-10Vdc
Maximum load
1mA
Output resistance
570
4x analog inputs (AI)
Types selectable via Jumper
resistance or voltage
Resistance:
Temperature range sensor type S.7
-50
C to +110
C
- accuracy (-25
C to +100
C)
<0.5
C
- accuracy (0
C to +60
C)
<0.2
C
Measuring range for position feedback
0-20k
Voltage:
Measuring range (input resistance 100k
)
0-10Vdc
Accuracy
+/- 15mVdc
4x Digital inputs (DI)
Open contact voltage
12Vdc
Low level
<1.0Vdc
Application: Counter input, min. pulse width 25mSec
max. frequency 20Hz
Application: Frequency input
max. frequency 5kHz
5 Digital outputs (Relays)
Relays 1, 2, 3 (make & break contact) and 4: voltage free
max. 2A 60Vdc/30Vac
Relay 5 (alarm relay): voltage free
max. 2A 60Vdc/30Vac
Extra digital outputs (DO)
Connection for optional relay (FRM.8 print).
Communication
I/O-Net for extra inputs and outputs using I/O-modules.
FNet, Fancom network for intercommunication of control computers and PC connection.
FRM.8
8 Digital outputs (relays)
Relay 1, 3, 5, 7: make-and-break contact
Max. 2A 60Vdc/30Vac
Relay 2, 4, 6, 8: voltage free
Max. 2A 60Vdc/30Vac
Other
Housing
Plastic housing with screw-on lid
IP54
Dimensions (l×w×h)
300×240×140mm
Weight (unpacked)
2.6kg
Ambient climate
Operating temperature range
0
C to +40
C (+32
F to +104
F)
Storage temperature range
–10
C to +50
C (+14
F to +122
F)
Relative humidity
< 95%, uncondensed
Summary of Contents for Lumina 35