Lumina 35
Explanation control functions
13
The fans which must activate at a certain ventilation position have been set in the relay or combi-table. However,
this means that the same fans will always be active. Using rotating the control computer will activate the number
of assigned fans, but in a different sequence each time. This creates an optimal spread of air in the house. In
addition, all fans are evenly used.
Rotating the sequence is impossible if all combi-relays (assigned for rotation) are activated.
The control computer has various heating controls that can be assigned independently.
Temperature zones in the house
A heater (blower) often only warms part of the house. It is better to divide the house into zones, and link certain
temperature sensors to the heater for this zone.
Separate setpoint heating
Usually one setpoint house temperature is used for ventilation and heating. The heating can also be given a
separate setpoint, the so-
called ‘extra temperature’. The extra temperature must be entered in the curve.
This may be necessary if floor heating is controlled based on temperature. In this case, the sensor measures a
different temperature to the actual house temperature.
High/low-control heating
Heaters can be linked together. Heater 1 is always the basis. For example, if heater 2 is linked to heater 1, these
heaters will always use the same actual setpoint. If the control value of heater 1 is changed, the control value of
heater 2 will change accordingly.
The above can also be used for low/high control. The control computer will activate the heaters one by one:
•
With a small difference between the control value of heater 1 and the house temperature, the control
computer will activate this heater.
•
As it gets colder, the difference increases. The control computer then activates extra heaters.
Enter to which analog inputs the temperature sensor(s) have been connected and to which outputs the heating
controls have been assigned. Also enter the type of control:
RELAY
or
ANALOG
. The type of control depends on
the heating system used. There are two relay controls (On/Off and modulating).
The controls used to control the heating are explained below.