The app menu <Settings>
Doc. no. BA012498_03
101 / 112
GB
If lights without light sensors are in use on one channel, the
manual setting
process has one restriction: Although you can still
use the slide controllers to set and save different brightnesses for
each channel, the lights will still produce the same brightness.
The reason: For lights without light sensors, brightness measure-
ment is only performed by the DALI detector. This means there is
only one measured brightness value that constant light manage-
ment uses for all channels.
13.3 Switching channels submenu
Switching channels control DALI switch devices that are connected to the
C1 and C2 DALI interfaces of the Light Control Box. Non-DALI-compatible
devices can be connected to the DALI switch devices. For example, you can
use the switching channel to switch on non-DALI-compatible blackboard
lighting in a classroom. The Light Control Boxes are configured in the fac-
tory to enable them to send commands via switching channels to connect-
ed DALI switches. In the Switching channels settings submenu, you can
change this setting and other settings.
For information on how to temporarily activate and deactivate the
switching channels, see Chapter “Switching the switching chan-
nels on and off” page 84.
The setting options are identical for both switching channels. You can make
the following settings:
13.3.1 Switching channel - Active
On. The Light Control Box sends control commands.
Off. The Light Control Box does not send control commands.
Limitation for
lights without
light sensors