Installation and connection
Doc. no. BA012498_03
34 / 112
GB
• After approx. 30 seconds, the Light Control Box is ready for operation
and functions in line with the factory settings or the user-defined
program.
Once the warm-up phase is complete, the LED signals on the
presence detector mean the following:
Red LED = remote control command is being received.
Green LED = presence detected.
Blue LED = Light Control Box is in programming mode.
4.6 Factory settings
The Light Control Boxes are configured with factory settings. These defaults
can be changed according to preference. ESYLUX recommends noting down
the changed settings in the right-hand column of the table.
Settings
Default
Individual setting
Operating mode
fully automatic
Brightness target value
500 lux
Off delay time
5 minutes
Orientation light
Brightness 10%
Duration of orientation light
0 minutes
Off warning channel 1–2
60 seconds
Colour temperature
4000 kelvin
SymbiLogic™
off
DALI channel 1 map
Master channel 1
(C1)
DALI channel 2 map
Slave channel 2
(C2)
DALI switch DS1
Active, mode: fully
automatic
Off delay time DS1
30 minutes
DALI switch DS2
Active, mode:
Semi-automatic
Off delay time DS2
30 minutes
4.7 Initial steps
The easiest way to configure your lighting system is to make the following
settings first:
•
Date and time:
The date and time must be set correctly before func-
tions such as the time-controlled orientation light and SymbiLogic™
will work. The time setting should be checked once a year. The set-
tings can be entered via the remote control (see Chapter 8.9) and via