7 Recorder Setup Utilities
7-12
TESLA LITE User Manual
D03283R01.10
AC Channel
Calibration
Process
To calibrate a channel (
Main Menu>Utilities>Analog Input Calibration)
:
1. Select the channel or channels from the list. More than one channel of volt-
age or current can be chosen using the
Control/Shift + left-click
.
2. Enter the voltage or current magnitude that is applied to the channel. The sig-
nal magnitude level should be measured with a precision calibrated instru-
ment.
3. Press the
Calibrate Offset
and
Gain
button. If a channel has not yet been con-
figured, only
Calibrate Offset
will be displayed.
4. Under the
Offset
and
Gain
columns the line of the channel being calibrated
OK
or
No
will be displayed (see “Analog Input Calibration” on page 7-11).
5. Repeat for all other channels being used.
6. Use the
Save
button to load the new calibration to the recorder.
Out of Range
An error message is displayed if the applied signal as seen by the recorder dif-
fers from the value entered in the Applied Signal
field by more than 10%. This
helps to prevent erroneous calibration.
It is possible to calibrate multiple channels simultaneously by using
the mouse to select a set of channels from the list. Multiple channels
can be selected using standard Windows selection methods.
Summary of Contents for tesla lite
Page 1: ...TESLA LITE Power System Recorder User Manual Version 1 1 Rev 0 ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ......
Page 12: ......
Page 20: ......
Page 24: ......
Page 78: ......
Page 126: ......
Page 134: ......
Page 214: ......
Page 234: ......
Page 280: ......
Page 284: ......
Page 288: ......